37
Drive Parameter Listing
(n005-n017)
Section 8
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
n005
Stop Method
0:
Ramp to stop
1
0
5.24
1:
Coast to stop
n006
Reverse Prohibit
0:
Reverse Run enabled
1
0
1:
Reverse Run disabled
0:
STOP
key is effective regardless of
programming of n003
n007
STOP Key Function
1:
STOP
key is effective only when sequence
1
0
5.13
command (per n003) is from Digital Operator
0:
Frequency Reference from digital
n008
Reference Selection -
operator pot
1
0
5.13
Digital Operator
1:
Frequency Reference from
n024
0:
ENTER
key must be pressed to write-in
n009
Frequency Reference Setting
new value
1
0
5.13
Method From Digital Operator 1:
ENTER
key does not have to be pressed
to write-in new value
Operation Selection
0:
Disabled (operation continues)
n010
When Digital Operator is
1:
Enabled (motor coasts to a stop and fault
1
0
5.15
Disconnected
is displayed)
n011
Frequency - Max.
50.0 to 400.0
0.1 (Hz)
60.0
n012
Voltage - Max.
0.1 to 255.0 (230V drive)
0.1 (V)
230.0
0.2 to 510.0 (460V drive)
460.0
n013
Frequency - Max.
0.2 to 400.0
0.1 (Hz)
60.0
Voltage Point
n014
Frequency - Midpoint
0.1 to 399.9
0.1 (Hz)
(Note 2)
5.27
n015
Voltage - Midpoint
0.1 to 255.0 (230V drive)
0.1 (V)
(Note 2)
0.2 to 510.0 (460V drive)
n016
Frequency - Min.
0.1 to 10.0
0.1 (Hz)
(Note 2)
n017
Voltage - Min.
0.1 to 50.0 (230V drive)
0.1 (V)
(Note 2)
0.2 to 100.0 (460V drive)
V7 Parameters - Continued
IG.V7.01_new format.qxd 4/18/05 1:21 PM Page 37
Summary of Contents for CIMR-V7xx20P1 series
Page 4: ...4 IG V7 01_new format qxd 4 18 05 1 21 PM Page 4...
Page 10: ...10 IG V7 01_new format qxd 4 18 05 1 21 PM Page 10...
Page 14: ...14 IG V7 01_new format qxd 4 18 05 1 21 PM Page 14...
Page 60: ...IG V7 01_new format qxd 4 18 05 1 21 PM Page 60...
Page 61: ...IG V7 01_new format qxd 4 18 05 1 21 PM Page 61...
Page 62: ...IG V7 01_new format qxd 4 18 05 1 21 PM Page 62...
Page 63: ...IG V7 01_new format qxd 4 18 05 1 21 PM Page 63...