Three-Phase 400 V Class Models 4A0930, 4A1200
+1
–
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
U/T1
V/T2
W/T3
+3
+
24 V
Power
Supply
DC link
choke
Relay
Gate board
Control
board
Operator
Current
sensor
Figure i.17 Connecting Main Circuit Terminals
Note:
Models 4A0930 and 4A1200 are compatible for operation with 12-phase rectification.
u
Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in
the drive.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices
could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus
charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the
drive on and off more than once every 30 minutes.
Refer to Factory Recommended Branch Circuit Protection for UL Compliance on page 107
for details on fuse selection.
u
Factory Recommended Branch Circuit Protection
WARNING! Fire Hazard. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply
could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more
than 100,000 RMS symmetrical amperes, 240 Vac (200 V class) and 480 Vac (400 V class), when protected by branch circuit protection
devices specified in this manual.
Branch circuit protection shall be provided by any of the following: Non-time delay Class J, T, or CC fuses sized at 300% of the drive input
rating, or Time delay Class J, T, or CC fuses sized at 175% of the drive input rating, or MCCB sized at 200% maximum of the drive input
rating.
Yaskawa recommends installing branch circuit protection according to maintain compliance with UL508C. Semiconductor
protective type fuses are preferred. Alternate branch circuit protection devices are also listed in this manual.
Recommended Branch Circuit Protection on page 98
i.4 Electrical Installation
24
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide