![YASKAWA CIMR-F7A Instruction Manual Download Page 159](http://html1.mh-extra.com/html/yaskawa/cimr-f7a/cimr-f7a_instruction-manual_3214306159.webp)
User Constant Tables
5-
49
* 1. Applicable for F7-series Inverters with software versions PRG:1032 or later.
* 2. Applicable for F7-series Inverters with software versions PRG:1031 or later.
Analog Inputs: H3
User constants for analog inputs are shown in the following table.
32
Speed control circuit operating for torque control (except when stopped).
The external torque reference will be limited if torque control is selected
(internal torque reference < external torque reference).
Output when the motor is rotating at the speed limit.
No
No
No
Yes 6-131
33
Zero-servo end (ON: Zero-servo function completed)
No
No
No
Yes
6-90
6-146
36
∗
1
Frequency (FOUT) detection 5
Yes
Yes
Yes
Yes
6-53
37
During run 2 (ON: Frequency output, OFF: Base block, DC injection brak-
ing, initial excitation, operation stop)
Yes
Yes
Yes
Yes
6-90
3D
∗
2
Inverter's Cooling Fan Fault detected
Yes
Yes
Yes
Yes
6-76
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
H3-01
Signal level
selection
(terminal
A1)
0: 0 to 10 V
1:
−
10 to 10 V
0 or 1
0
No
A
A
A
A
410H 6-35
H3-02
Gain (termi-
nal A1)
Sets the frequency when 10
V is input, as a percentage of
the maximum output fre-
quency.
0.0 to
1000.0
100.0%
Yes
A
A
A
A
411H 6-35
H3-03
Bias (termi-
nal A1)
Sets the frequency when 0 V
is input, as a percentage of
the maximum frequency.
-100.0
to
+100.0
0.0%
Yes
A
A
A
A
412H 6-35
H3-04
Signal level
selection
(terminal
A3)
0: 0 to 10 V
1:
−
10 to 10 V
0 or 1
0
No
A
A
A
A
413H
6-35
6-130
H3-05
Multi-func-
tion analog
input (ter-
minal A3)
function
selection
Select from the functions
listed in the following table.
Refer to the next page.
0 to 1F
1F
No
A
A
A
A
414H
6-35
6-130
H3-06
Gain (termi-
nal A3)
Sets the input gain (level)
when 10V is input.
Set according to the 100%
value selected from H3-05.
0.0 to
1000.0
100.0%
Yes
A
A
A
A
415H
6-35
6-130
H3-07
Bias (termi-
nal A3)
Sets the input gain (level)
when 0V is input.
Set according to the 100%
value selected from H3-05.
-
100.0
to
+100.0
0.0%
Yes
A
A
A
A
416H
6-35
6-130
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor