Application Overview 2-12
#
Operational Mode – nciOpModeRun
Table 2.10 - Operational Mode - nciOpModeRun
Property Name
Variable Type
Default
Parameter
Description
nciOpModeRun SNVT_count
0
b1-02
Selects location of the Run/Stop command
Table 2.11 - nciOpModeRun
nciOpModeRun
Run Command Source
Remarks
0 Digital
Operator
nviDrvSpeedStpt
has no effect
1 External
Terminals
nviDrvSpeedStpt
has no effect
2
Serial Communications (
L
ON
W
ORKS
)
nviDrvSpeedStpt
is controlled via the network
3 Option
Card
nviDrvSpeedStpt
has no effect
#
Operational Mode – nciOpModeFreqRef
Table 2.12 - Operational Mode - nciOpModeRun
Property Name
Variable Type
Default
Parameter
Description
nciOpModeFreqRef SNVT_count
0 b1-01
Selects
location of the frequency reference command
Table 2.13 - nciOpModeFreqRef
nciOpModeFreqRef
Run Command Source
Remarks
0 Digital
Operator
nviDrvSpeedScale
has no effect
1 External
Terminals
nviDrvSpeedScale
has no effect
2
Serial Communications (
L
ON
W
ORKS
)
nviDrvSpeedScale
is controlled via the network
3 Option
Card
nviDrvSpeedScale
has no effect
4 Pulse
Input
nviDrvSpeedScale
has no effect (Available on F7 and G7 only)
#
Motor Properties – nciNmlSpeed, nciNmlFreq, nciMaxSpeed, nciMinSpeed,
nciMtrFLA
These properties define the motor characteristics, configuring the drive as described below:
Table 2.13 - Motor Properties – nciNmlSpeed, nciNmlFreq, nciMaxSpeed, nciMinSpeed, nciMtrFLA
Property Name
Variable Type
Default
Parameter
Description
nciNmlSpeed
SNVT_rpm
1800 rpm
n/a
Configures nominal motor speed in rpm.
nciNmlFreq SNVT_freq_hz 60
Hz
n/a Configures nominal motor frequency in hertz. All speed related data in
percent are referenced to this value.
nciMinSpeed SNVT_lev_percent 0%
d2-02
Configures the minimum motor speed as a percentage of
nciNmlFreq
. Sets
the drive’s lower limit for frequency commands.
nciMaxSpeed SNVT_lev_percent 100%
d2-01
Configures the maximum motor speed as a percentage of
nciNmlFreq
.
Sets the drive’s upper limit for frequency commands.
nciMtrFLA SNVT_amp
*
E2-01
Sets the full load current rating of the motor.
* Value is dependent on drive capacity. Refer to appropriate parameter access and/or technical manual.
Summary of Contents for CIMR-E7 series
Page 1: ...LONWORKS Option Technical Manual Models CIMR E7 P7 F7 and G7 Document Number TM AFD 20 ...
Page 5: ...iv This page intentionally left blank ...
Page 7: ...Installation 1 2 This page intentionally left blank ...
Page 9: ...Installation 1 4 This page intentionally left blank ...
Page 19: ...Application Overview 2 2 This page intentionally left blank ...
Page 38: ...Diagnostics 3 2 This page intentionally left blank ...
Page 40: ...Diagnostics 3 4 This page intentionally left blank ...