Installation 1-12
Drive Faults
The following is a table of faults that could be caused by the
L
ON
W
ORKS
Option
that will be displayed on the Operator Keypad, their causes, and
possible solutions. For any fault displayed on the operator that is not listed in the following table, please see the appropriate drive technical
manual.
Table 1.4 – Drive Faults
Fault
Content
Cause
Solution
BUS
Option PCB communications error
Communication is not established between
L
ON
W
ORKS
Master and the drive.
%
Check L
ON
W
ORKS
communication LED display.
EF0
Option PCB external fault
Drive received an external fault command
from the Option PCB
%
Check multi-function input settings
%
Check PLC or controller program
%
Eliminate cause of fault (machine device in fault state)
OPE05
Command selection fault
Parameter b1-01 is set to Option PCB and no
card is detected
%
Install Option PCB
%
Reprogram b1-01
%
Replace the Option PCB
OPE06
Control mode selection fault
Parameter b1-02 is set to Option PCB and no
card is detected
%
Install Option PCB
%
Reprogram b1-02
%
Replace the Option PCB
Summary of Contents for CIMR-E7 series
Page 1: ...LONWORKS Option Technical Manual Models CIMR E7 P7 F7 and G7 Document Number TM AFD 20 ...
Page 5: ...iv This page intentionally left blank ...
Page 7: ...Installation 1 2 This page intentionally left blank ...
Page 9: ...Installation 1 4 This page intentionally left blank ...
Page 19: ...Application Overview 2 2 This page intentionally left blank ...
Page 38: ...Diagnostics 3 2 This page intentionally left blank ...
Page 40: ...Diagnostics 3 4 This page intentionally left blank ...