Application Overview 2-6
Table 2.3 - VFD Object Network Variable Summary
Index
Variable Name
Variable Type
Description
nv14
nvoSpdStptFb
SNVT_lev_percent Reports the speed setpoint as a percentage of nciNmlFreq
nv15
nvoSpdCmd
SNVT_lev_percent Reports the speed command as a percentage of nciNmlFreq regardless of command source
nv16
nvoPIDFb
SNVT_lev_percent Reports the PID feedback as a percentage of nciNmlFreq
nv17
nvoDrvBus
SNVT_volt
Reports DC Bus voltage
nv18 nvoReadParamVal SNVT_count
Reports
value of requested parameter
nv19
nviDrvFltRst
SNVT_switch
Resets a drive fault
nv20
nvoRunStp
SNVT_switch
Reports the Run/Stop status of the drive
nv21 nvoDrvFlt SNVT_switch
Reports drive fault condition
nv22
nvoDrvParamErr
SNVT_count
Reports parameter access error
nv23
nvoDrvTemp
SNVT_temp
Reports drive temperature
nv24
nvoDrvEnergyKwh
SNVT_elec_kwh Reports cumulative energy in kWh
nv25
nvoDrvEnergyMwh
SNVT_elec_kwh Reports cumulative energy in mWh
#
Parameter Access Errors
These values are returned by nv22 when a communications error occurres.
!
0 -
Normal
!
2 -
Incorrect register error
!
33 - Data range error
!
34 - Parameter not writable in Run mode
!
35 – Write when drive is in Undervoltage
!
36 – Process busy
!
255 - Command timeout error
Summary of Contents for CIMR-E7 series
Page 1: ...LONWORKS Option Technical Manual Models CIMR E7 P7 F7 and G7 Document Number TM AFD 20 ...
Page 5: ...iv This page intentionally left blank ...
Page 7: ...Installation 1 2 This page intentionally left blank ...
Page 9: ...Installation 1 4 This page intentionally left blank ...
Page 19: ...Application Overview 2 2 This page intentionally left blank ...
Page 38: ...Diagnostics 3 2 This page intentionally left blank ...
Page 40: ...Diagnostics 3 4 This page intentionally left blank ...