YASKAWA
SIEP C730600 83E CC-Link Technical Manual
45
Monitor Code (Hex.)
Name
Comments
1000
Number of pulse 1 speed detection
-
1001
Number of pulse 2 speed detection
-
1002
Cumulative operation time
-
1003
Watt-hour output (lower digits)
-
1004
Watt-hour output (upper digits)
-
1010
Alarm code
-
1011
Fault code
-
1012
Reserved
-
1013
Fault contents 1
-
1014
Fault contents 2
-
1015
Fault contents 3
-
1016
Fault contents 4
-
1017
Fault contents 5
-
101C
CPF contents 1
-
101D
CPF contents 2
-
101E
CPF contents 3
-
101F
Alarm contents 1
-
1020
Alarm contents 2
-
1021
Alarm contents 3
-
1022
Alarm contents 4
-
1023
Alarm contents 5
-
1027
Output frequency at previous fault
-
1028
Output current at previous fault
-
1029
Output voltage at previous fault
-
102A
Cumulative operation time at previous fault
-
*1
Terminals are different for different drive models. Refer to
Terminals that Change depending on the Model of the Drive on page 35
for more information.
*2
Refer to
Drive Fault Contents on page 45
or
Drive Alarm Contents on page 48
for information on fault contents.
■
Drive Fault Contents
Table 10.4 Drive Fault Contents
Extended Command Code
(Monitor Code) (Hex.)
Name
Fault Code (U2, U3) (Hex.)
BIT
120 (1013)
Fault contents 1
-
0
Reserved
-
1
Uv1 [DC Bus Undervoltage]
0002
2
Uv2 [Control Power Undervoltage]
0003
3
Uv3 [Soft Charge Answerback Fault]
0004
4
SC [Short Circuit/IGBT Failure]
0005
5
Reserved
-
6
oC [Overcurrent]
0007
7
ov [Overvoltage]
0008
8
oH [Heatsink Overheat]
0009
9
oH1 [Heatsink Overheat 1]
000A
A
oL1 [Motor Overload]
000B
B
oL2 [Drive Overload]
000C
C
oL3 [Overtorque Detection 1]
000D