SIEP C730600 83E CC-Link Technical Manual
31
Signal
Name
Description
Comments (Default)
RXB
Monitoring Motor Revolutions
ON: Currently monitoring motor revolutions.
Data is stored in remote register
RW
R1
.
RXC
Obtain Monitor Data
ON: Monitor data has been updated.
-
RXD
Frequency Setting Ready 1
ON: Displays the main frequency reference that has been set.
-
RXE
Frequency Setting Ready 2
ON: Displays the data set to
d1-01 [Frequency Reference 1]
.
Note:
Also sets the main frequency reference at the same time.
-
RXF
Command Code Execute
Complete
ON: Displayed after the specified command code has been executed.
RXF signal switches OFF when the RYF command is no longer present.
-
RX10 - 19
Reserved
-
-
RX1A
Error
ON: Fault occurred on the drive side.
-
RX1B
Remote Station Ready
ON: Drive is ready to operate.
-
RX1C - 1F
Reserved
-
-
*1
Terminals are different for different drive models. Refer to
Terminals that Change depending on the Model of the Drive on page 35
for more information.
Note:
If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. Using RYE (Frequency Reference 2
flag) too often can shorten the performance life of the drive's internal memory.
■
D1000 Remote I/O
PLC → D1000
Table 8.3 Remote I/O List (PLC → D1000)
Signal
Name
Description
Comments (Default)
RY0
Run Command/Automatic Run
Command
ON: Run Command/Automatic Run Command
OFF: Stop Command
-
RY1
Forced Run Command
ON: Forced Run Command
OFF: Stop Command
-
RY2
Terminal S3 Function
Multi-Function Input: H1-03
H1-03 = 24 [External Fault]
RY3
Terminal S4 Function
Multi-Function Input: H1-04 [Terminal S4 Function Selection]
H1-04 = 14 [Fault Reset]
RY4
Terminal S5 Function
Multi-Function Input: H1-05
H1-05= F [Through Mode]
RY5
Terminal S6 Function
Multi-Function Input: H1-06
H1-06= F [Through Mode]
RY6
Terminal S7 Function
Multi-Function Input: H1-07
H1-07= F [Through Mode]
RY7
Terminal S8 Function
Multi-Function Input: H1-08
H1-08 = 8 [Baseblock command
(N.O.)]
RY8
Reserved
-
-
RY9
External Baseblock Command
ON: No converter output
-
RYA
External Fault [EF0]
ON: Option Card External Fault
-
RYB
Reserved
-
-
RYC
Monitor Reference
ON: Monitor data specified in the monitor code is set to remote register RW
R0
.
When switching between
monitors using RYC (Monitor
Reference), RYC needs to be
turned OFF and then back ON
again after the monitor code has
been changed.
RYD, E
Reserved
-
-
RYF
Command Code Execute Request
Request to execute the command code.
Triggered by the rising edge of
the signal.
RY10
Terminal M1-M2 Function
Multi-Function Relay Output 1 (Terminal M1-M2)
-
RY11
Terminal P1-PC Function
Multi-Function Photocoupler Output 1 (Terminal P1-PC)
-
RY12
Terminal P2-PC Function
Multi-Function Photocoupler Output 2 (Terminal P2-PC)
-
RY13
Reserved
-
-
RY14
Terminal S1 Function
Multi-Function Input: H1-01
H1-01 = 4B [Run Command]
RY15
Terminal S2 Function
Multi-Function Input: H1-02 [Terminal S2 Function Selection]
H1-02 = 4C [Stop Command]
RY16
RY17 Enabled/Disabled Selection
-
-