21
4. COMMUNICATION REFERENCE TABLE
Reference
No.
FNC
Code
R/W
Data name
Setting range
(in-transmission)
46001
03
06
R
W
Operation mode:
Remote/local
0: Fixed temp operation
1: Fixed temp auto start
2: Fixed temp auto stop
3: Program operation
4: Program auto start
5: Local (at the time of writing, and the end of mode)
◆
Remote mode start setting is not available when
local control is ON.
◆
Remote mode can only be cancelled while in remote
mode.
◆
Program operation
For program auto start:
Setting not available unless program patterns are set.
46002
03
06
R
W
Operation mode:
STOP/RUN
STOP/RUN (0/1)
◆
No processing in local mode.
46003
03
06
R
W
Communication
protocol select
ASCI/RTU (0/1)
◆
It does not depend on communication impossibility
conditions.
46004
03
06
R
W
Data length setting
7BIT/8BIT(0/1)
◆
It does not depend on communication impossibility
conditions.
◆
7BIT cannot be set while RTU is being set.
46005
03
06
R
W
Parity setting
NON/ODD/EVN (0/1/2)
◆
It does not depend on communication impossibility
conditions.
46006
03
06
R
W
Stop bit setting
1BIT/2BIT (0/1)
◆
It does not depend on communication impossibility
conditions.
46007
03
06
R
W
Communication rate
setting
9.6k/19.2k/38.4kbps (3/4/5)
◆
It does not depend on communication impossibility
conditions.
46008
03
06
R
W
Response delay time
setting
0/10/20-240/250ms (10 increments)
(0/1/2-24/25)
◆
It does not depend on communication impossibility
conditions.
46009
03
06
R
W
Address setting
1-99 (1-99)
◆
It does not depend on communication impossibility
conditions.
46010
03
06
R
W
Communication mode
setting
R/RW (0/1)
◆
It does not depend on communication impossibility
conditions.