Table 7. Proc_Cal_005: Lower Valve Output Threshold (Continued)
Action 2:
SLOWLY Activate (Feather) Lower Control.
Action 3:
WATCH for Attachment Movement. When it first starts to move slowly, HOLD control steady and.....
Press
*
One Time while holding the control.
Action 4:
STOP activating the Lower Control. LOOK at the display.
Go to the Calibration Step below that matches your display.
If You See.....
Result out of range
Repeat Calibration
Press
*
One Time
You Will See:
Lower Valve Output
Press
*
at Creep
Return to Action 2. Perform Actions 2 through 4 again.
If You See.....
Tilt Bk Valve Output
Press
*
at Creep
To Continue with Calibrations.....
Go to Action 3 of Proc_Cal_006.
To Quit and Save....
Step 1: Press
or
Until You See:
Tilt Bk Valve Output
Back 1 Level
Step 2: Press
*
One Time
You Will See:
Calibrations
Back 1 Level
Perform Proc_Cal_003: Save and Exit.