Automatic Mode

Automatic Mode

successfully completed. If you are in automatic mode, you can select
from three degassing programs, if required. System monitoring is active
with all three programs. Make-up takes place automatically. Selection in
customer menu.

Continuous degassing

– Intensive degassing following start-up and

repairs.
The degassing cycles are executed successively for the set
continuous degassing time (basic setting: 5 h). The controller then
automatically proceeds with interval degassing. In the case of water
systems, at least half the system volume should flow through the
’servitec’ unit once during start-up. Based on a system volume of
8 m

3

, this is equivalent to approx. 22 h of continuous degassing. In

systems that are particularly rich in gas, a continuous degassing
period of 48 h is completely sufficient. As a result of the subsequent
interval degassing, 10,000 intervals are made per year. This number
per year must not be exceeded in order to avoid unnecessary wear to
the ’servitec’. The controller registers the total number of intervals that
have passed.

Interval degassing

– Economy mode in automatic mode

After 8 intervals (standard), a break (standard 23 h) is observed
before the next 8 degassing intervals are started. This program is
automatically started upon completion of continuous degassing or can
be selected manually for systems already degassed. Interval
degassing then starts at 08:00 each day.

No degassing

– Only make-up

The system water is not degassed. This operating mode is practical
during summer operation or if general degassing of the system water
is not required.

Manual mode may only be be used after the initial start-up has been
completed. This operating mode is primarily a means of performing
functional checks of the pump and the make-up solenoid valve.

Select the pump or motorized ball valve,
activate the flashing symbol with the “ok”
button.

Pump starts/motorized ball valve opens.

Pressing the “ok” button again stops the
pump or closes the motorized ball valve.
Alternatively, the “quit” button can also be
pressed directly. The pump and motor-
ized ball valve then switch off after each
other.

Stop Mode

In stop mode, ’servitec 30’ is without function except for indication in the
LCD display. Operation monitoring does not take place. The pump is shut
off. The adjacent display appears when the “stop” button is pressed.

Summary of Contents for Lowara Servitec

Page 1: ...mentioned above The following instructions must be read and understood by all persons responsible for the installation operation and maintenance of this product Warning Symbols Safety instructions wh...

Page 2: ...must be made using the appropriate wiring drawings for the equipment being installed with particular attention being paid to the supply voltages The supply voltage is shown on the set duty plate Neve...

Page 3: ...will work independently of the Lowara Servitec unit In this case the water make up port 3 can be blanked off and not used It is possible to connect a basic fill unit to the system for water make whic...

Page 4: ...4 Specific system set points The display shows the servitec type selected servitec magcontrol or servitec levelcontrol The system type can be specified here Select levelcontrol System fill pressure...

Page 5: ...5 Select continuous gassing time And confirm with OK button Select the degassing program Confirm with OK button Select the degassing program Confirm with OK button...

Page 6: ...6 Configure the setting here for whether a water meter is to be evaluated e g when using Lowara fillset with contact meter 0 Only alarm Factory settings 1 Alarm messages...

Page 7: ...7 The last 20 errors including error code e g ER01 page 11 are shown here as well as the relevant operating hours until the message occurs E01 is the most recent error E20 is the oldest...

Page 8: ...on temperature can be read off the displaY after a short time This is possible because the pump 6 draws more water from the pump casing than is able to flow in via the pressure supply port with nozzle...

Page 9: ...nterval degassing Economy mode in automatic mode After 8 intervals standard a break standard 23 h is observed before the next 8 degassing intervals are started This program is automatically started up...

Page 10: ...of the messages are automatically acknowledged once the cause has been remedied see table Errors such as Make up time 06 or Make up cycle 07 must be acknowledged manually For remote transmission it is...

Page 11: ...ory use Maintenance instructions Disassembly Maintenance work should only be carried out by specialists As a reminder of the annual maintenance the message SrV is shown in the display after a year of...

Page 12: ...97 630230 Fax 01297 630270 e mail lowaraukenquiries xyleminc com http www lowara co uk http completewatersystems com Lowara is a trademark of Xylem Inc or one of its subsidiaries 2011 Xylem Inc Lowara...

Reviews: