Xylem Lowara Servitec Installation, Operating And Maintenance Instructions Download Page 2

Installation

The Lowara Servitec unit is despatched mounted on a wooden pallet and covered in a protective film, it is

recommended that the unit be retained in the protective packaging until the product is to be 
installed. The unit will arrive pre-packaged and wired ready for installation.
This product has been fully run tested at our works under simulated site conditions. The unit
should be thoroughly checked for physical damage that may have been caused during transit.
If the unit is found to have damage it must be reported immediately and should not be installed.

The unit must be sited in a clean well ventilated area with good all round access, two fixing holes are 
provided in the back plate allowing the unit to be wall mounted.

Electrical Connections

The cable used for the incoming supply must be of adequate size to carry the motor full load current. This is

shown on the duty plate. All non power caballing should be limited to 2.5mm².
All connections must be made using the appropriate wiring drawings for the equipment being 
installed, with particular attention being paid to the supply voltages.
The supply voltage is shown on the set duty plate.

Never operate this product with the control panel front cover removed.
It is essential that this equipment is earthed to the building earth system.
Pumps operate at 230v 50Hz

All wiring should be arranged such that it enters the control section through the appropriate cable glands.

2

Important:
Despite removing the mains plug, 230 V 
may still be present at terminal 10, 11 12, 
13 and 14, and at parts of the circuit board.

Fuse

Electronics

Fuse

Motor

Designation

Terminal

Signal

Note

Supply

1

PE

(230 V)

2

N

’servitec’ is fully wired with a shock-proof plug

3

L

Make-up motorized 
ball valve

4

Y1

5

N

connected

6

PE

Pump

7

M1

8

N

connected

9

PE

External make-up 
control

10

only for ’servitec levelcontrol’ mode 
230 V wire on site

11

Common message

12

NC

(fl oating)

13

COM

wire on site 

(optional)

14

NO

Not confi gured

15

+24 V DC

not wired up

16

E1

Water shortage

17

+24 V DC

not connected 

(jumper)

switch

18

E1

Pressure measure-
ment transducer

19

+18 V

connected

20

AE

Terminal Diagram

Summary of Contents for Lowara Servitec

Page 1: ...mentioned above The following instructions must be read and understood by all persons responsible for the installation operation and maintenance of this product Warning Symbols Safety instructions wh...

Page 2: ...must be made using the appropriate wiring drawings for the equipment being installed with particular attention being paid to the supply voltages The supply voltage is shown on the set duty plate Neve...

Page 3: ...will work independently of the Lowara Servitec unit In this case the water make up port 3 can be blanked off and not used It is possible to connect a basic fill unit to the system for water make whic...

Page 4: ...4 Specific system set points The display shows the servitec type selected servitec magcontrol or servitec levelcontrol The system type can be specified here Select levelcontrol System fill pressure...

Page 5: ...5 Select continuous gassing time And confirm with OK button Select the degassing program Confirm with OK button Select the degassing program Confirm with OK button...

Page 6: ...6 Configure the setting here for whether a water meter is to be evaluated e g when using Lowara fillset with contact meter 0 Only alarm Factory settings 1 Alarm messages...

Page 7: ...7 The last 20 errors including error code e g ER01 page 11 are shown here as well as the relevant operating hours until the message occurs E01 is the most recent error E20 is the oldest...

Page 8: ...on temperature can be read off the displaY after a short time This is possible because the pump 6 draws more water from the pump casing than is able to flow in via the pressure supply port with nozzle...

Page 9: ...nterval degassing Economy mode in automatic mode After 8 intervals standard a break standard 23 h is observed before the next 8 degassing intervals are started This program is automatically started up...

Page 10: ...of the messages are automatically acknowledged once the cause has been remedied see table Errors such as Make up time 06 or Make up cycle 07 must be acknowledged manually For remote transmission it is...

Page 11: ...ory use Maintenance instructions Disassembly Maintenance work should only be carried out by specialists As a reminder of the annual maintenance the message SrV is shown in the display after a year of...

Page 12: ...97 630230 Fax 01297 630270 e mail lowaraukenquiries xyleminc com http www lowara co uk http completewatersystems com Lowara is a trademark of Xylem Inc or one of its subsidiaries 2011 Xylem Inc Lowara...