Table 20: Models MMA and MTA
Parame-
ter
Descrip-
tion
Range
Unit of
meas-
urement
Default
Pr
Propor-
tional co-
efficient
of the
PID reg-
ulator (*)
2 to 100 -
19
ACCEL-
ER.
Acceler-
ation
time.
Minimum
time re-
quired
for the
frequen-
cy of the
motor to
go from
minimum
to maxi-
mum fre-
quency.
2 to 15
Hz/sec
10
DECEL-
ER.
Deceler-
ation
time.
Minimum
time re-
quired
for the
frequen-
cy of the
motor to
go from
minimum
to maxi-
mum fre-
quency.
2 to 15
Hz/sec
10
FREQ.S
W.
Selection
of the
switching
frequen-
cy of the
power
mod-
ule.**
4 / 8
kHz
8
DE-
FAULT
PAR
Select
YES to
set the
default
values
NO/YES -
NO
RESET
CONT.
Select
YES to
reset the
operation
counters
and the
alarm
log.
NO/YES -
NO
SET
PRESS
Set the
required
0.5 to 10
0.0 to 16
bar
2.5
Parame-
ter
Descrip-
tion
Range
Unit of
meas-
urement
Default
pressure
value of
the sys-
tem (set
point)
(in rela-
tion to
the full
scale of
the sen-
sor)
MIN.PRE
SS
Pressure
value of
the sys-
tem be-
low
which
the
A4
"mini-
mum
pres-
sure"
alarm is
trig-
gered.
When
the alarm
is trig-
gered,
the pump
stops
and the
ART
function
is ena-
bled.
See
.
Trigger-
ing of the
alarm is
delayed
by the
length of
time set
in the
MP DE-
LAY
pa-
rameter.
0.0 to
(
SET
PRESS
-0.4)
0.0 =
Disabled
bar
0.0
(*) these values depend on the type of installation
and are compatible with all the various types of sys-
tem.
(**) The noise level of the motor can be reduced us-
ing a frequency of 8 kHz. Increasing the switching
frequency reduces the capacity of the converter. It is
advisable to use a frequency of 4 kHz when the mo-
tor cable is long, in order to minimize the capacitive
currents in the cable.
WARNING:
Editing the parameters can cause the
converter to malfunction. Contact the as-
sistance service when modifications are
required.
5.4 Special functions
en - Original instructions
37
Summary of Contents for Lowara ResiBoost MMW Series
Page 229: ...15 4 20mA QCL5 Max Min Max Min G WH BN inst m_03 SC BP it en fr de es pt nl pl el tr 229 ...
Page 234: ...22 INST G_11_B SC 7 6 5 4 3 2 1 13 8 11 12 2 10 11 2 14 15 it en fr de es pt nl pl el tr 234 ...
Page 235: ...23 INST G_12_B SC 1 2 7 15 14 6 5 4 3 8 9 2 10 11 12 18 13 it en fr de es pt nl pl el tr 235 ...
Page 236: ...24 INST G_13_B SC 2 1 13 8 11 12 2 10 11 2 14 15 16 11 17 it en fr de es pt nl pl el tr 236 ...
Page 237: ...25 13 15 14 INST G_14_B SC 8 9 2 1 2 10 11 12 18 17 16 11 it en fr de es pt nl pl el tr 237 ...
Page 243: ......