6.5.8 Test Run Configuration Parameters
Test Run is a function that starts the pump after the last stop, in order to prevent it from blocking.
No. Parameter
Unit of
measurement
Description
P65 Test Run – Time Start
[0-100]
h
This parameter sets the time after which, once the pump has
stopped for the last time, the Test Run will start.
Default: 100 h.
P66 Test Run – Speed
[P27-Max]
rpmx10
This parameter sets the pump rotational speed for the Test Run.
The Min and Max speeds depend on the pump type.
Default: 200 rpmx10.
P67 Test Run – Time
Duration [0-180]
s
This parameter sets the duration of the Test Run.
Default: 10 s.
6.5.9 Special Parameters
No. Parameter
Unit of
measurement
Description
P68 Default Values Reload
[NO, RES]
If set to RES, after confirmation this parameter performs a
factory reset that reloads the default parameter values.
P69 Avoid Frequent
Parameters Saving [NO,
YES]
This parameter limits the frequency with which the unit stores
the required value P02 in the EEPROM memory, in order to
extend its life.
This could be particularly useful in applications with BMS
control devices that require continuous variation of the value
for fine tuning purposes.
Default: NO.
6.5.10 Example: ACT control mode with analog input
Graph
Figure 13: ACT control mode diagram
Table 13: Description
No.
Description
1
ZERO point (0Vdc - 4mA) = minimum analog signal value
2
Adjustment start point
3
Standby point (SBY) = 1/3 of the hysteresis zone
4
ON point (ON) = 2/3 of the hysteresis zone