6.5 Software parameters
Parameters are marked differently in the manual depending on their type:
Mark
Parameter type
No mark
Applicable to all units
Read only
6.5.1 Status Parameters
No. Parameter
Unit of
measurement
Description
P01 Required value
bar/psi/ rpmx10
This parameter shows the SOURCE and the VALUE of the
active required value.
Visualization cycles between SOURCE and VALUE occur
every 3 seconds.
SOURCES:
SP (SP): required internal Setpoint value related to the
control mode selected
VL (UL): external required speed Setpoint value, related
to the 0-10V input.
VALUE can represent a Speed or a Head, depending on the
selected control mode:
in case of Head, the unit of measure is defined by
parameter P41.
P05 Operating time months
Total months of connection to the electric mains, to add to
P06.
P06 Operating time hours h
Total hours of connection to the electric mains, to add to
P05.
P07 Motor Time Months
This parameter shows the total operating time months, to
be added to P08.
P08 Motor time hours
h
This parameter shows the total operating time hours, to be
added to P07.
P09 1st error
This parameter stores the last error occurred in
chronological order.
The information displayed switches through the values:
(Exx): xx indicates the error code
(Hyy): yy is the value of hours referred to P05-P06 when
the error Exx happened
(Dww): ww is the value of days referred to P05-P06
when the error Exx happened
(Uzz): zz is the value of weeks referred to P05-P06
when the error Exx happened
Example of visualisation:
E04
K10
d03
U15
P10 2nd error
Saves the penultimate error in chronological occurred.
Other characteristics: like P09.
P11 3rd error
Saves the third from the last error in chronological
occurred.
Other characteristics: like P09.
P12 4th error
Saves the fourth from the last error in chronological
occurred.
Other characteristics: like P09.
P13 Power Module
°C
Temperature of the power module.