P1323 IND.INVERTER
Imposta l'indirizzo desiderato (l'impostazione possi-
bile è compresa tra 1 e 247) per l'interfaccia utente.
L'utente può configurare nuovamente l'indirizzo, nel
caso in cui questo sia stato sovrascritto in un siste-
ma a pompa multipla.
1 Operation
1.1 Startup checklist
1. Install the unit on the motor fan cover, keeping
motor cable as short as possible.
2. Fasten the unit using the mounting clamps and
relative screws
3. Connect the drive to the power supply ; con-
nect, if necessary, all the needed auxiliary input/
output signals of the drive. See
30).
4. Take care of some particular connection exam-
ples, related to sensors:
a) using an active sensor, see
(page
31).
b) using a passive sensor, see
(page
31).
c) using 2 passive sensors, see
(page
32).
5. In case a serial communication is required, take
care of some particular connection examples:
a) for a serial connection to an external device,
see
(page 32).
b) for a serial connection for multi-pump applica-
tion, see
(page 33).
6. If the application requires to use the status relay
contacts, follow the connection example in
7. When the Premium Card is available, connect, if
necessary, all the needed auxiliary input/output
signals of the card. See
(page 34).
8. If HYDROVAR is fitted with the additional Premi-
um Card, take care of the connection example
to connect 3 fixed speed pumps to the Premium
(page 35).
9. Power the drive, wait for Xylem logo to disap-
pear and then proceed with configuring the
Startup Submenu M1300.
1.2 Submenu M1300
P1301 LANGUAGE
English
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1301 LANGUAGE
This parameter selects the display language.
P1302 MOTOR NOM.POWER
1.5 kW
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1302 MOTOR NOM.POWER
This parameter sets the nominal power of the motor
coupled with HYDROVAR, as reported on the motor
nameplate.
P1303 MOTOR NOM.VOLT.
230 V
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1303 MOTOR NOM.VOLT.
Sets the motor nominal voltage, as reported in the
motor nameplate, according to
• the chosen motor connection
• the output voltage of the HYDROVAR
P1304 PRE-SET MOTOR ?
YES
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1304 PRE-SET MOTOR?
By selecting "
Yes
", the user is declaring the use of a
Lowara IE3 surface 2-poles motor 50Hz (without
Motor Filter): in this case, the motor's electrical pa-
rameters are already available to HYDROVAR, so
the start-up procedure skips to P1308
STC MOTOR
PROT.
.
By selecting "NO", the user is declaring the use of
any other motor: in this case the motor's electrical
parameters need to be set into HYDROVAR, so the
start-up procedure goes to the next step (P1305
MOTOR NOM.CURR.
)
P1305 MOTOR NOM.CURR.
7.5 A
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1305 MOTOR NOM.CURR.
Sets the motor nominal current, as reported in the
motor nameplate, according to
• the chosen motor connection
• the output voltage of the HYDROVAR
en - Original instructions
5