P1306 MOTOR NOM.SPEED
3000 rpm
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1306 MOTOR NOM.SPEED
Sets the motor nominal speed, as reported in the
motor nameplate.
P1307 AMPI
Full
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1307 AMPI
This parameter activates the Automatic Motor Pa-
rameter Identification; possible settings are "Off"
(
AMPI
not active), "Full" or "Reduced" (procedure to
be performed only in case LC filters are applied on
the motor cable).
For this parameter please note that, once entered in-
to edit mode (by pressing the provided push button),
the user can confirm the new value by pressing for 3
sec the right (►) push button.
P1308 STC MOTOR PROT.
STC Trip
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1308 STC MOTOR PROT.
This parameter sets the protection technique against
motor overheating; possible the settings are "Ther-
mistor trip" or "STC trip" (default).
P1309 MODE
Controller
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1309 MODE
This parameter selects which operating mode to set
the unit to.
P1310 PUMP ADDR.
1
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1310 PUMP ADDR.
This parameter selects an address (1-8) for each
HYDROVAR. If several inverters are connected via
the internal RS-485 connection (maximum eight in
Cascade serial mode), then the following must ap-
ply:
• Each HYDROVAR needs an individual pump-ad-
dress (1–8)
• Each address can only be used once.
P1311 CONTROL MODE
Constant
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1311 CONTROL MODE
For this parameter please note that, once entered in-
to edit mode (by pressing the provided push button),
the user can confirm the new value by pressing for 3
sec the right (►) push button.
This parameter sets the pressure control mode for
the pump system (single and multi pump): depend-
ing on the setting ("Constant" or "Differential") a set
of further parameters are automatically configured.
Whenever P1311
CONTROL MODE
is set to a new
value, each parameter in the below table is overwrit-
ten to its own specified value, regardless of previous
different settings.
P1311 = Con-
stant
P1311 = Differ-
ential
P225
RAMP 3
70 sec
90 sec
P230
RAMP 4
70 sec
90 sec
P250
MIN.FREQ.
20 Hz
25 Hz
P315
HYSTE-
RESIS
80%
90%
P410
CONF.SENSOR
Sensor 1
Sens.1 - Sens.
2
P1312 DIMENSION UNIT
bar
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1312 DIMENSION UNIT
Selects the unit of measure for the system.
P1313 START-UP COMPLETED?
No
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P1313 START-UP COMPLETED?
If the application is a multi-pump, then the startup
procedure for the first [N-1] pumps is stopped here
when selecting Yes.
If the application is a single-pump or the last pump
of a Multi-pump, then select No .
P1314 SENSOR RANGE
en - Original instructions
6