![Xylem GOULDS RGS Series Installation, Operation And Maintenance Instructions Download Page 6](http://html1.mh-extra.com/html/xylem/goulds-rgs-series/goulds-rgs-series_installation-operation-and-maintenance-instructions_4202148006.webp)
6
FLOAT SWITCH AND PANEL CHART
The purpose of this chart is to show the required switch
quantities and the function of each switch in a typical
wastewater system. The quantities required vary de-
pending on the switch type, single-action or wide-angle.
Switch quantities also vary by panel type: simplex with
and without alarms, and duplex with alarms.
Duplex Panels using single-action switches:
Three Float Panel Wiring
SW1
Bottom
Pumps Off
SW2
Middle
1st Pump On
SW3
Top
2nd Pump & Alarm On
Four Float Panel Wiring
➁
SW1
Bottom
Pumps Off
SW2
2nd
1st Pump On
SW3
3rd
2nd Pump On
SW4
Top
Alarm On
Duplex Panels using wide-angle switches:
Three Float Panel Wiring
SW1
Bottom
1st Pump On/Both Off
SW2
Top
2nd Pump & Alarm On
Four Float Panel Wiring
SW1
Bottom
1st Pump On/Both Off
SW2
Middle
2nd Pump On
SW3
Top
Alarm On
Simplex Panel using single-action switches:
Simplex Panel with Alarm
①
SW1
Bottom
Pump Off
SW2
Middle
Pump On
SW3
Top
Alarm On/Off
Simplex Panel with No Alarm
SW1
Bottom
Pump Off
SW2
Top
Pump On
Simplex Panel using wide-angle switches:
Simplex Panel with Alarm
SW1
Bottom
Pump On/Off
SW2
Top
Alarm On/Off
Simplex Panel with No Alarm
SW1
Pump On/Off
Inlet
Alarm SW3
Pump On SW2
Pump Off SW1
Discharge
Inlet
Alarm SW4
Lag Pump On
SW3
Pump Off
SW1
Discharge
Lead Pump On
SW2
Simplex
➀
Duplex
➁
Summary of Contents for GOULDS RGS Series