Xylem GOULDS RGS Series Installation, Operation And Maintenance Instructions Download Page 4

4

PIPING

Discharge piping should be no smaller than the pump 

discharge diameter and kept as short as possible,   

avoiding unnecessary fittings to minimize friction losses.
Install an adequately sized check valve to prevent fluid 

backflow. Backflow can allow the pump to “turbine” back

-

wards and may cause premature seal and/or bearing 

wear. If the pump is turning backwards when it is called 

on to start the increased torque may cause damage to 

the pump motor and/or motor shaft and some single-

phase pumps may actually run backwards.
Install an adequately sized gate valve 

AFTER

 the check 

valve for pump, plumbing and check valve maintenance.

Important – Before pump installation.

 If pumping waste 

water containing solids, drill a  

3

16

” (4.8mm) relief hole in 

the discharge pipe. It should be located within the wetwell, 

2” (51mm) above the pump discharge but below the 

check valve. The relief hole allows any air to escape from 

the casing. Allowing liquid into the casing will insure that 

the pump can start when the liquid level rises. Unless a re-

lief hole is provided, a bottom intake pump could “air lock” 

and will not pump water even though the impeller turns.
All piping must be adequately supported, so as not to 

impart any piping strain or loads on the pump.

The pit access cover must be of sufficient size to allow for 

inspection, maintenance and crane or hoist service.

WIRING AND GROUNDING

Important notice: Read Safety Instructions before 

 

proceeding with any wiring.

Use only stranded copper wire to pump/motor 

and ground. The ground wire must be at least 

as large as the power supply wires. Wires should 

be color coded for ease of maintenance and  

troubleshooting.
Install wire and ground according to the National 

Electrical Code (NEC), or the Canadian Electrical 

Code, as well as all local, state and provincial codes.
Install an all leg disconnect switch where required 

by code.
Disconnect and lockout electrical power before 

performing any service or installation.
The electrical supply voltage and phase must 

match all equipment requirements. Incorrect volt-

age or phase can cause fire, motor and control 

damage, and voids the warranty.
All splices must be waterproof. If using splice kits 

follow manufacturer’s instructions.

Select the correct type and NEMA grade 

junction box for the application and loca-

tion. The junction box must insure dry, 

safe wiring connections.
Seal all controls from gases present which 

may damage electrical components.

FAILURE TO PERMANENTLY       

GROUND THE PUMP, MOTOR AND   

CONTROLS BEFORE CONNECTING          

TO POWER CAN CAUSE SHOCK, 

BURNS OR DEATH.

SELECTING AND WIRING  

PUMP CONTROL PANELS AND SWITCHES

FLOAT SWITCH TYPES

There are two types of float switches available for use 

with 2 HP, single phase grinder pumps; single action con-

trol switches and wide angle mechanical switches.
Single action control switches can only be connected 

through a control panel. Connecting them directly to a 

pump will cause rapid cycling and may burn up the mo-

tor, and/or the motor start switch and/or the float switch. 

If using single action switches with a control panel please 

see the 

Float Switch and Panel Section.

Model A2G33 wide angle pump float switches can be 

hard wired directly to the pump. Wide angle switches can 

operate the pump via connection to a control panel. The 

tether length or distance from the switch body to the piv-

ot point controls the On and Off points and the amount 

pumped in one cycle. The pivot point is where the float is 

attached to the discharge pipe. 

See Figures 1 and 2.

SETTING THE FLOAT SWITCHES

There are no absolute rules for where to set the float 

switches, it varies from job to job.  

Suggested Rules to Follow:

All floats should be set below the Inlet pipe!

Off Float:

 Best: set so the water level is always above the 

top of the pump (motor dome). 

Next Best:

 set so the wa-

ter level is not more than 6” below the top of the pump. 

On Float:

 set so the volume of water between the On 

and Off floats allows two (2) HP and larger pumps to run 

a minimum of 2 minutes. Basin literature states the gal-

lons  

of storage per inch of basin height. 

Lag/Alarm Float(s):

 should be staggered above the 

Off and On floats. Try to use most of the available stor

-

age provided by the basin, save some space for reserve 

storage capacity. 

See Diagrams and Charts in Float Switch 

Chart Section.

PANEL WIRING DIAGRAMS

Our control panels are shipped with instructions and 

wiring diagrams. Use those instructions in conjunction 

with this IOM. Electrical installation should be performed 

only by qualified technicians. Any problem or questions 

pertaining to another brand control must be referred 

to that control supplier or manufacturer. Our technical 

people have no technical schematics or trouble shooting 

information for other companies’ controls.

ALARMS

We recommend the installation of an alarm on all Waste-

water pump installations. Many standard control panels 

come equipped with alarm circuits. If a control panel is 

not used, a stand alone high liquid level alarm is avail-

able. The alarm alerts the owner of a high liquid level in 

the system so they can contact the appropriate service 

personnel to investigate the situation.

WARNING

Hazardous 
voltage

WARNING

WARNING

Summary of Contents for GOULDS RGS Series

Page 1: ...Single Phase Single Seal Grinder Pump INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS INSTRUCTION MANUAL IM038R07 ...

Page 2: ...Installation Checks 3 Lifting of Pump 3 Optional Guide Rail or Lift Out System 3 Piping 4 Wiring and Grounding 4 Selecting and Wiring Pump Control Panels and Switches 4 5 Installation 5 Operation 5 6 Float Switch and Panel Chart 6 Engineering Data 7 Insulation Resistance Readings 8 Typical Installations and Simplex Wiring Diagrams 8 9 Troubleshooting 10 Limited Warranty 11 Owner s Information ...

Page 3: ...HECKS Open all cartons and inspect for shipping damage Report any damage to your supplier or shipping carrier immediately Important Always verify that the pump nameplate Amps Voltage Phase and HP ratings match your control panel and power supply Many of our sewage pumps are oil filled If there are any signs of oil leakage or if the unit has been stored for an extended period check the oil level in...

Page 4: ... AND CONTROLS BEFORE CONNECTING TO POWER CAN CAUSE SHOCK BURNS OR DEATH SELECTING AND WIRING PUMP CONTROL PANELS AND SWITCHES FLOAT SWITCH TYPES There are two types of float switches available for use with 2 HP single phase grinder pumps single action con trol switches and wide angle mechanical switches Single action control switches can only be connected through a control panel Connecting them di...

Page 5: ...ontrols and alarms to the end user Leave the paperwork with the owner or at the control panel if in a dry secure location SINGLE PHASE PUMPS PLUG CONNECTED UNITS MUST BE CONNECTED TO A PROPERLY GROUNDED GROUNDING TYPE RECEPTACLE ON NON PLUG UNITS DO NOT RE MOVE CORD AND STRAIN RELIEF DO NOT CONNECT CONDUIT TO PUMP Pumps with bare lead power cords can be hard wired to a float switch wired to a 1Ø c...

Page 6: ...mp On SW3 3rd 2nd Pump On SW4 Top Alarm On Duplex Panels using wide angle switches Three Float Panel Wiring SW1 Bottom 1st Pump On Both Off SW2 Top 2nd Pump Alarm On Four Float Panel Wiring SW1 Bottom 1st Pump On Both Off SW2 Middle 2nd Pump On SW3 Top Alarm On Simplex Panel using single action switches Simplex Panel with Alarm SW1 Bottom Pump Off SW2 Middle Pump On SW3 Top Alarm On Off Simplex Pa...

Page 7: ...ase use the control panel drawings in conjunction with this instruction manual to complete the wiring Minimum Submergence Continuous Duty Fully Submerged Intermittent Duty 6 Below Top of Motor Maximum Fluid Temperature Continuous Operation 104º F 40º C Intermittent Operation 140º F 60º C 6 15 3 cm 6 15 3 cm 8 20 3 cm TURN ON LEVEL WEIGHT Single Action Float Switch Typical Installation Figure 4 Pum...

Page 8: ...ries very little with rating Motors of all HP voltage and phase ratings have similar values of insulation resistance Insulation resistance values above are based on readings taken with a megohmmeter with a 500V DC output Readings may vary using a lower voltage ohmmeter consult factory if readings are in question SERVICE POLE CONTROL PANEL INLET HUB MERCURY SWITCH HIGH LEVELALARM OPTIONAL MERCURY S...

Page 9: ... PINK NEU TEST T RED FOR SEPARATE 120 VAC CONTROL POWER SUPPLY REMOVE JUMPER J1 FROM TERMINALS H AND L1 CONNECT15 AMP MAX PROTECTED 120 VAC SUPPLY TO TERMINALS L1 AND N WITH THE NEUTRAL OF THE SUPPLYTO N FOR USE WITH WIDE ANGLE FLOAT SWITCH ONE FLOAT FOR BOTH ON AND OFF OPERATION JUMP TERMINALS 3 AND 4 INSTALL WIDE ANGLE FLOAT TO TERMINALS 1 AND 2 FLASH REPLACE WITH 1A FUSE ONLY 1A A FUSED DISCONN...

Page 10: ... level cords tangled Untangle cords and insure free operation TURN OFF Pump is air locked Shut off pump for approximately one minute then restart Repeat until air lock clears If air locking persists in a system with a check valve a 3 16 4 8 mm hole may be drilled in the discharge pipe approximately 2 51 mm above the discharge connection Influent flow is matching pump s Larger pump may be required ...

Page 11: ...11 ...

Page 12: ...proper electrical protection or g damaged resulting from the use of accessory equipment not sold or approved by Seller In any case of products not manufactured by Seller there is no warranty from Seller however Seller will extend to Buyer any warranty received from Seller s supplier of such products Goulds Water Technology Policy Concerning Online Sales to Consumers Homeowners using the Internet t...

Page 13: ...13 Bomba trituradora monofásica de sello único INSTRUCCIONES DE INSTALACIÓN FUNCIONAMIENTO Y MANTENIMIENTO MANUAL DE INSTRUCCIÓN IM038R07 ...

Page 14: ...de la bomba 14 Riel de guía o sistema de levantamiento opcional 14 Tuberías 15 Alambrado y conexión a tierra 15 Selección y cableado de los interruptores y paneles de control de la bomba 15 Instalación 16 Operación 17 Tabla del panel e interruptores de flotador 18 Datos de ingeniería 19 Lecturas de resistencia de la instalación 20 Instalaciones típicas y diagramas de cableado de la bomba de diseño...

Page 15: ... listas de agencias PELIGRO ADVERTENCIA PRECAUCIÓN Desconecte y bloquee la corriente eléc trica antes de instalar o dar servicio a cual quier equipo eléctrico Muchas bombas están equipadas con protección automática contra la sobrecarga térmica la cual podría permitir que una bomba demasiado cali ente rearranque inesperadamente VERIFICACIONES PRELIMINARES A LA INSTALACIÓN Abra todas las cajas e ins...

Page 16: ...o montacargas ALAMBRADO y CONEXIÓN A TIERRA Aviso importante Lea las instrucciones de seguridad antes de proseguir con el cableado Use únicamente alambre trenzado de cobre para la bomba motor y la conexión a tierra El alambre de conexión a tierra debe ser al menos del mismo tamaño que los alambres de la fuente de aliment ación Los alambres deben codificarse con colores para facilitar el mantenimie...

Page 17: ...stalar los interruptores de flotador varía de trabajo a trabajo Reglas sugeridas a seguir Todos los flotadores de ben instalarse debajo de la tubería de entrada Flotador de apagado Primera preferencia instálelo de manera que el nivel del agua quede siempre sobre el extremo superior de la bomba cúpula del motor Se gunda preferencia instálelo de manera que el nivel del agua quede a no más de 6 pulg ...

Page 18: ... en la sección delantera de este manual para referencia futura Compare las lecturas de amperaje con el amperaje máxi mo indicado en la placa de identificación de la bomba Si es más alto que el amperaje de la placa de identificación investigue la causa Si la bomba se hace funcionar fuera de la curva es decir con demasiado poca carga o con tensión alta o baja aumentará el amperaje El motor funcionar...

Page 19: ...cendidas Cableado del panel de cuatro flotadores SW1 Fondo Bombas apagadas SW2 Segundo Primera bomba encendida SW3 Tercero Segunda bomba encendida SW4 Extremo superior Alarma encendida Paneles dobles utilizando interruptores de ángulo amplio Cableado del panel de tres flotadores SW1 Fondo Primera bomba encendida ambas apagadas SW2 Extremo superior Segunda bomba y alarma encendidas Cableado del pan...

Page 20: ...ente Servicio intermitente 6 pulg por debajo del extremo superior del motor Temperatura máxima del fluido Operación continua 104º F 40º C Operación 140º F 60º C intermitente 6 pulg 15 3 cm 6 pulg 15 3 cm PESO NIVEL DE ENCENDIDO 8 pulgadas 20 3 CM Interruptor de flotador de acción simple Instalación típica Figure 4 Rango de bombeo Interruptor de flotador de ángulo amplio Enchufe de los interruptore...

Page 21: ...nto Los valores de resistencia de aislamiento anteriores están basados en lecturas obtenidas con un megaohmió metro con salida de 500 V CC Las lecturas pueden variar utilizando un ohmiómetro de tensión más baja con sulte con la fábrica si tiene dudas acerca de las lecturas CONEXIONES E INSTALACIÓN TÍPICA POSTE DE SERVICIO PANEL DE CONTROL CUBO DE ENTRADA INTERRUPTOR DE MERCURIO ALARMA POR ALTO NIV...

Page 22: ... WHT WHT PINK NEU TEST T RED FOR SEPARATE 120 VAC CONTROL POWER SUPPLY REMOVE JUMPER J1 FROM TERMINALS H AND L1 CONNECT15 AMP MAX PROTECTED 120 VAC SUPPLY TO TERMINALS L1 AND N WITH THE NEUTRAL OF THE SUPPLYTO N FOR USE WITH WIDE ANGLE FLOAT SWITCH ONE FLOAT FOR BOTH ON AND OFF OPERATION JUMP TERMINALS 3 AND 4 INSTALL WIDE ANGLE FLOAT TO TERMINALS 1 AND 2 FLASH REPLACE WITH 1A FUSE ONLY 1A A FUSED...

Page 23: ...SEAPAGA delíquidoenredados funcionamientolibre Labombaestáatascadaconaire Apaguelabombaduranteaproximadamenteunminuto yarránquelanuevamente Repitahastaquesedespejela obstruccióndeaire Silaobstruccióndeairepersisteen unsistemacontuboconválvuladeretención puede perforarseunagujerode3 16 pulg 4 8mm eneltubo dedescargaaproximadamentea2pulgadas 51mm de laconexióndedescarga Elflujodelíquidoentrantecoinc...

Page 24: ...s no vendidos ni aprobados por el Vendedor En el caso de productos no fabricados por el Vendedor no habrá Garantía del Vendedor sin embargo el Vendedor transferirá al Comprador toda Garantía recibida del proveedor del Vendedor para dichos productos Política de Goulds Water Technology sobre ventas en línea a clientes Los propietarios que utilizan Internet para encontrar información sobre sistemas d...

Page 25: ...25 Pompe dilacératrice broyeuse monophasée à simple garniture mécanique DIRECTIVES D INSTALLATION D UTILISATION ET D ENTRETIEN MANUEL D UTILISATION IM038R07 ...

Page 26: ...26 Système de levage optionnel à rail de guidage ou à adaptateur coulissant 27 Tuyauterie 27 Câblage et mise à la terre 27 Sélection et câblage des contacteurs et des tableaux de commande 27 Installation 28 Mise en marche 29 Tableaux de commande et fonction des contacteurs à flotteur 30 Données techniques 31 Valeurs de résistance d isolement du moteur 32 Installations types et schémas de câblage m...

Page 27: ... feuillets du catalogue décrivant les pompes en question Verrouiller la source de courant en position ouverte avant de procéder à l installation ou à l entretien de tout dispositif électrique Le protecteur thermique de certains moteurs de pompe coupe le cou rant lorsqu il y a surcharge thermique et le rétablit automa tiquement redémarrant ainsi la pompe inopinément VÉRIFICATIONS AVANT INSTALLATION...

Page 28: ...mpêcheraient le pompage du liquide même si la roue de la pompe tourne La tuyauterie doit être supportée correctement pour n appliquer sur la pompe aucune charge pouvant la déformer Couvercles et trappes de visite doivent être assez grands pour permettre l inspection et l entretien de la pompe ainsi que l emploi d un dispositif de levage CÂBLAGE ET MISE À LA TERRE Avis important lire les Consignes ...

Page 29: ...odes aux règlements locaux et aux illustrations de la section Installations types AVERTISSEMENT Les tensions dangereuses peuvent causer un choc électrique des brûlures et la mort Les contacteurs à la pompe à flotteur à grand déplacement angulaire modèle A2G33 peuvent être branchés par raccordement fixe directement à la pompe Modèles de ce type de contacteur peuvent être reliés à la pompe par le ta...

Page 30: ...bleau de commande alimenté en courant monophasé de 230 V empêchera le circuit de commande du tableau de fonc tionner Le neutre est nécessaire pour alimenter 115 V le circuit de commande Mesurer l intensité et la tension du courant au démar rage et les inscrire à titre documentaire dans les Informa tions pour le propriétaire en première page Comparer l intensité mesurée à l intensité maximale indiq...

Page 31: ... flotteur SW1 Inférieur 1re pompe en fonction ou les deux hors fonction SW2 Supérieur 2e pompe et alarme en fonction Quatre contacteurs à flotteur SW1 Inférieur 1re pompe en fonction ou les deux hors fonction SW2 Intermédiaire 2e pompe en fonction SW3 Supérieur Alarme en fonction Tableaux de commande pour pompe simple à contacteurs à simple effet Trois contacteurs à flotteur avec alarme SW1 Inféri...

Page 32: ...imale Service continu Immersion totale Service intermittent 6 po sous le dessus du compartiment moteur Température maximale du liquide Service continu 40 C 104 F Service intermittent 60 C 140 F 15 3 cm 6 po 15 3 cm 6 po NIVEAU DE DÉMARRAGE 20 3 cm 8 po POIDS Installation type à contacteur à flotteur à simple effet Figure 4 Plage de pompage Contacteur à flotteur à grand déplacement angulaire Fiche ...

Page 33: ... résistance d isolement ci dessus sont tirées de mesures prises avec un mégohmmètre et une tension de sortie de 500 V c c Les valeurs mesurées peuvent varier si l on utilise un ohmmètre avec une tension moindre Communiquer avec le personnel technique de l usine en pareil cas INSTALLATIONS TYPES POTEAU D AMENÉE DE COURANT TABLEAU DE COMMANDE BRIDE D ENTRÉE CONTACTEUR À MERCURE ALARME NIVEAU HAUT EN...

Page 34: ...WHT PINK NEU TEST T RED FOR SEPARATE 120 VAC CONTROL POWER SUPPLY REMOVE JUMPER J1 FROM TERMINALS H AND L1 CONNECT15 AMP MAX PROTECTED 120 VAC SUPPLY TO TERMINALS L1 AND N WITH THE NEUTRAL OF THE SUPPLYTO N FOR USE WITH WIDE ANGLE FLOAT SWITCH ONE FLOAT FOR BOTH ON AND OFF OPERATION JUMP TERMINALS 3 AND 4 INSTALL WIDE ANGLE FLOAT TO TERMINALS 1 AND 2 FLASH REPLACE WITH 1A FUSE ONLY 1A A FUSED DISC...

Page 35: ...escâblesdecontacteuràflotteurets assurer LAPOMPE àflotteurenchevêtrés quelescontacteurspeuventbougerlibrement Poched airdanslapompe Arrêterlapompependantenvironuneminute puisla remettreenmarche Répéterl opérationjusqu àcequela poched airs élimine Sileproblèmepersisteetquele tuyauderefoulementcomporteunclapetdenon retour onpeutperceruntrou purgeurd airde4 8mm 3 16 po dediamètredansletuyauàenviron51...

Page 36: ...endeur il n y a aucune garantie de la part du Vendeur toutefois le Vendeur prolongera à l Acheteur toute garantie reçue du fournisseur du Vendeur de tels produits Politique de Goulds Water Technology concernant les ventes en ligne aux clients Les propriétaires de maison utilisant l Internet pour trouver des informations concernant les systèmes d eau résidentielle les systèmes d eaux usées résident...

Reviews: