WARNING: Crush Hazard
Risk of automatic restart.
If the communication fails and the unit continues to operate, then turn off the power
supply to the pump. For more information, see
4. Use the software application interface to read and write data.
on page 48.
5. To disconnect the software application, select Disconnect.
The pump starts and the software application stops to communicate with the pump.
6. Turn on and off again the power supply to the pump.
Upgrade the software application
1. Uninstall previous versions of the software application.
See Control Panel > Programs and Features > Dirigo Service Tool.
2. Contact the local sales and service representative for the latest version of the
application.
3. Run the executable file on the PC.
8.2 The pump does not start
DANGER: Crush Hazard
Moving parts can entangle or crush. Always disconnect and lock out power before
servicing to prevent unexpected startup. Failure to do so could result in death or serious
injury.
Equipment
locked
out
by
Name
.......................
DANGER
WARNING: Electrical Hazard
The permanent-magnet motor generates voltage when the shaft rotates, even if power
sources are disconnected. Never perform any electrical work if the shaft could rotate.
Cause
Remedy
The installation is not receiving voltage.
Check that:
• The main power switch is on.
• The fuses are intact.
• There is voltage in all phases of the supply line.
• All fuses have power and are securely fastened to the
fuse holders.
• The motor cable is not damaged.
The sum alarm is active.
Contact a sales or authorized service representative or use
the Dirigo
™
Service Tool application to read the alarm
codes.
If the problem persists, then contact a sales or authorized service representative.
8 Troubleshooting
50
6020.180/090 Installation, Operation, and Maintenance Manual