Sensor connection characteristics
The values have a 10 % tolerance.
Sensors
Value (mA)
Definition
FLS and thermal contact
0
Overtemperature
7.8
OK
36
Leakage
CLS and thermal contact
0
Overtemperature
5.5
OK
29
Leakage (5 seconds delay)
CLS, FLS and thermal contact
0
Overtempterature
13.3
OK
36–42
Leakage (0/5 seconds delay)
Check the impeller rotation
WARNING:
The starting jerk can be powerful.
1. Start the motor.
2. Stop the motor after a few seconds.
3. Check that the impeller rotates according to this illustration.
Installation
30
Flygt 5520 Installation, Operation, and Maintenance Manual