Cable charts
Connection locations
1 2 3 4 5 6 7
1 2
L1 L2 L3
GC
U1 W2 V1 U2
T16 T15 T2 T1
W1 V2
1
2
3
6
5
4
7
1.
Control leads
2.
Starter equipment
3.
Mains leads
4.
Motor cable
5.
Terminal blocks on pump
6.
Stator leads
7.
Control cable
Colors and marking of the mains leads
Mains
SUBCAB 7GX
SUBCAB 4GX
SUBCAB AWG
L1
Black 1
Brown
Red
L2
Black 2
Black
Black
L3
Black 3
Grey
White
Yellow/Green
Yellow/Green
Yellow/Green
Groundcheck (GC)
-
-
Yellow
Color and marking of the control leads
Control
SUBCAB 7GX and SUBCAB 4GX
SUBCAB AWG
T1
White T1
Orange
T2
White T2
Blue
Colors of the stator leads
Stator connection
Lead color
U1
Red
U2
Green
U5
Red
V1
Brown
V2
Blue
Installation