AC6102 Rev 0
5
22
7.6.2.4
9100 series Horizontal Split Case maximum forces and moments allowed
Size
Maximum forces (F) in lbf (N) and moments (M) in lbf.ft (Nm)
Suction
Discharge
F
x
F
y
F
z
M
x
M
y
M
z
F
x
F
y
F
z
M
x
M
y
M
z
12X8X21
193
242
167
226
282
565
79
98
108
92
115
230
(858)
(1076)
(743)
(306)
(382)
(766)
(351)
(436)
(480)
(125)
(156)
(312)
12X8X22
193
242
167
226
282
565
79
98
108
92
115
230
(858)
(1076)
(743)
(306)
(382)
(766)
(351)
(436)
(480)
(125)
(156)
(312)
14X10X20
571
714
284
666
833
1666
196
245
160
207
259
518
(2540)
(3176)
(1263)
(903)
(1130)
(2259)
(872)
(1090)
(712)
(281)
(351)
(702)
16X12X23
623
779
323
865
1081
2163
215
268
192
298
373
746
(2771)
(3465)
(1437)
(1173)
(1466)
(2933)
(956)
(1192)
(854)
(404)
(506)
(1012)
Summary of Contents for AC Fire Pump 8100 Series
Page 2: ...Series 8100 8150 8200 9100 Fire Pump 1 AC6102 Rev 05...
Page 4: ...Series 8100 8150 8200 9100 Fire Pump 3 AC6102 Rev 05...
Page 8: ...Series 8100 8150 8200 9100 Fire Pump 7 AC6102 Rev 05...
Page 41: ...AC6102 Rev 05 40 Table 14 Troubleshooting List...
Page 50: ...Series 8100 8150 8200 9100 Fire Pump 49 AC6102 Rev 05 A Appendix...