Using the repeater function

 

 
The ANE01 has three options for repeating: 
 

1)  No repeating (default), both dip-switches to OFF (number side) 
2)  Repeat only original telegrams (level 1), only dipswitch 1 to ON 
3)  Repeat original and 1-time repeated telegrams: both dipswitches to ON 

 
A disconnect and reconnect of the power of the ANE01 is required before changes to these 
dipswitches will take effect. 
 

Verifying the enOcean antenna 

 
When the beta firmware is installed, the enOcean function will automatically be activated. 
This option can be turned on or off on the basic settings page of the xxter unit. On the status 
page you can see whether xxter has properly recognised and connected to the antenna. 
 
 

Short introduction to the enOcean telegram format 

 
With the new configuration tool you can configure enOcean components. Every enOcean 
device (a switch, actor, dimmer, sensor, etc.) can either transmit or receive telegrams or do 
both. 
 
Every telegram has a sender address and a channel number, which is used to identify every 
device. In xxter you can create an alias for every device, for easier recognition.  
 
Every enOcean telegram also has a specific type and function, which depends on the used 
hardware of the device. xxter now supports a great number of different types of telegrams 
and more will added in the near future. In case you want to apply a certain type of hardware 
that is not yet supported, please inform us and we will add it to the configuration options. 
 
For xxter it is important to know which types of telegrams are supported by which device. 
Newer devices will automatically supply the type of the telegram, when the device is teached 
in. Older devices however do not support this feature and the type needs to be selected 
manually. 
 
To look up the telegram type, a list of all supported brands and devices are included in 
addendum 2. In case you cannot find the device you want to configure, please let us know so 
we can further expand this list. 
 

Summary of Contents for enOcean ANE01

Page 1: ... latest configuration tool version 1 8 3 or newer 4 The latest firmware version 1 8 3 or newer Connecting the antenna The enOcean ANE01 antenna has a serial connector and a power split cable which both need to be connected Please follow the following instructions 1 Make sure the xxter is disconnected from the power 2 Attach the serial connector of the ANE01 to the serial RS232 port of your xxter 3...

Page 2: ...either transmit or receive telegrams or do both Every telegram has a sender address and a channel number which is used to identify every device In xxter you can create an alias for every device for easier recognition Every enOcean telegram also has a specific type and function which depends on the used hardware of the device xxter now supports a great number of different types of telegrams and mor...

Page 3: ...e which value to use xxter uses letters in addition to the telegram Every letter stands for another value in the telegram and can be found in addendum 1 For instance a switch RPS can have one button A and another button B or a CO2 sensor BS4 09 04 will have A as the CO2 concentration B as the temperature and C as the humidity Using the xxter configuration tool In the configuration tool open a proj...

Page 4: ...ected since every type of telegram will always have at least one value The letter can be changed manually if needed TIP to quickly connect telegrams to actions select the proper status field before sending receiving the teach telegram This will automatically connect the received telegram to this action When a switch is pressed the specific switch telegram will be sent and also the right letter wil...

Page 5: ...re 128 channels available in a range from 0 to 127 When a switch telegram RPS is used four buttons van be used per channel Therefore there are a total of 128 4byte telegrams 512 switch commands or a combination of the two possible This restriction only applies to the sending telegrams When sending 4byte telegrams the appropriate type and function also need to be configured To teach a device the ne...

Page 6: ...ction In this action fill in the enOcean telegram as the sending group address and teach in the telegram at the required enOcean device In the status field fill in the KNX group address and in the bridge column select the option on change or always When selecting the bridge option on change an enOcean telegram will only be sent when the value changes When selecting the option always any received t...

Page 7: ... Temperature sensor range 40 to 80 C A Temperature C A Temperature sensor range 50 to 90 C A Temperature C B Temperature sensor range 60 to 100 C A Temperature C 10 Temperature sensor range 60 to 20 C A Temperature C 11 Temperature sensor range 50 to 30 C A Temperature C 12 Temperature sensor range 40 to 40 C A Temperature C 13 Temperature sensor range 30 to 50 C A Temperature C 14 Temperature sen...

Page 8: ... Humidity B Temperature C 2 Temperature range 20 to 60 C and humidity 0 100 A Humidity B Temperature C 6 Light sensor 1 Range 300lx to 60 000lx A Illumination lux B Supply voltage V 2 Range 0lx to 1020lx A Illumination lux B Supply voltage V 7 Occupancy sensor 1 Occupancy A Occupancy 0 1 8 Light temperature and occupancy sensor 1 Range 0lx to 510lx 0 to 51 C and occupancy A Temperature C B Illumin...

Page 9: ... Temperature C 4 CO2 sensor A Concentration ppm B Temperature C C Humidity 10 Room operating panel Not yet available 11 Not yet available 12 Automated meter reading 0 Counter A Counter value B Current value 1 s C Measurement channel 0 15 1 Electricity A Cumulative value kWh B Current value W C Tariff info 0 15 2 Gas A Cumulative value m3 B Current value l s C Tariff info 0 15 3 Water A Cumulative ...

Page 10: ...change A Day 1 31 B Month 1 12 C Year 2000 2099 D RTC GPS or eq 0 1 4 Time and date exchange A Weekday 1 Monday 7 Sunday B Hour 0 23 C Minute 0 59 D Second 0 59 E 24 or 12 hours 0 1 F AM or PM 0 1 G RTC GPS or eq 0 1 5 Direction exchange A Elevation 90 to 90 0 horizon B Azimut 0 to 359 0 north 6 Geographical position exchange A Latitude 90 90 B Longitude 180 180 20 HVAC Components Not yet availabl...

Page 11: ...w basic setpoint 0 51 2 C L Control variable override 0 100 M Controller mode 0 auto 1 heating 2 cooling 3 off N Controller state 0 auto 1 override O Energy hold off 0 normal 1 energy hold off dew point P Occupancy 0 occupied 1 unoccupied 2 standby Q Fanspeed 0 3 or 255 255 auto These telegrams are only send with the bold character 1 Central switch variant for Eltako and Opus Greennet A Block swit...

Page 12: ...1VA 10A RPS B FSU12D RPS B FSR70W 16A RPS B FSU55D RPS B FTN61NP 230V RPS B FKC RPS A FLX61NP 230V RPS B FKF RPS A FUD61NP 230V RPS B FRW RPS A BS4 38 08 FSS12 BS4 12 01 0x02 dim E FT4 1 toets RPS B FUD61NPN 230V RPS B FT4F 1 toets RPS B BS4 38 08 FT55 1 toets RPS B 0x02 dim E FT4 2 toetsen RPS A B FT4F 2 toetsen RPS A B Eltako FLC61 230V BS4 38 01 FT55 2 toetsen RPS A B central FSB12 not supp yet...

Page 13: ...ess button 7 release button 7 L press button 8 release button 8 M 1 toggle by press N 2 toggle by press O 3 toggle by press P 4 toggle by press Q 5 toggle by press R 6 toggle by press S 7 toggle by press T 8 toggle by press Enocean xxter Example switchs with two up down buttons k1 k3 k2 k4 How to program k1 ON k2 OFF Type Name Sending Status Switch S1 ENO 0 A ENO 0 F How to program to two toggle f...

Reviews: