REPLACING THE BATTERY
(QUALIFIED SERVICE PERSONNEL ONLY)
CAUTION!
Read and follow the IMPORTANT SAFETY INSTRUCTIONS before
servicing the battery. Service the battery under the supervision of Qualified Service
Personnel knowledgeable of batteries and their precautions.
CAUTION!
Use only the specified type of battery. See your dealer for replacement
batteries.
CAUTION!
The battery may present risk of electrical shock. Do not dispose of
battery in a fire, as it may explode. Follow all local ordinances regarding proper
disposal of batteries.
CAUTION!
Do not open or mutilate the batteries Released electrolyte is harmful to
skin and eyes and may be toxic.
CAUTION!
Although the battery system voltage is only 12VDC and 24VDC, the
battery can present a high risk of short circuit current and electrical shock. The
short circuit current capability of the battery is sufficient to burn wire or tools very
rapidly producing molten metal. Observe these precautions when replacing the
battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. Do not lay tools or metal parts on top of battery or any terminals.
4. Wear protective eye gear (goggles), rubber gloves and boots.
5. Disconnect the charging source before connecting or disconnecting the b a t t e r y
terminals.
6. Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove the source of ground. Contact with a grounded battery can result in
electrical shock! The likelihood of such shock will be reduced if; such grounds
are removed during installation and maintenance (applicable to a UPS and a
remote battery supply not having a grounded circuit).
BATTERY REPLACEMENT PROCEDURE
(QUALIFIED SERVICE PERSONNEL ONLY)
Note:
The XVT-600, the XVT-800, the XVT-1200, and the XVT-1500 have user
replaceable batteries.
1. Turn off and unplug all connected equipment.
2. Turn the UPS off and unplug the UPS's power cord from the AC wall outlet.
3. Turn the UPS upside down.
4. Remove the retaining screws from the battery compartment door.
5. Remove the battery compartment door.
.
-
10
-