XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation
Page 82
•
Make all necessary connections (see Fig. 75 on previous page).
•
Switch on the UPS or go back to normal from maintenance bypass.
Interfaces
UPT 10/100 – RJ45 Port
Connection to an Ethernet 10/100 Mbps network using a UTP cable.
RS-232 – DB9 Port
Serial communication connection to a local console.
Use a straight (1:1) serial cable for connection to a PC
CONNECTOR PIN OUT AS FOLLOWS:
PIN #
FUNCTION
2
TD – TRANSMIT DATA
3
RD – RECEIVE DATA
5
GND
Configuration
Configuration via serial connection
•
Connect the SNMP/Web Card to a computer using a standard 1:1 serial communications cable.
•
Run a terminal simulator (e.g. HyperTerminal on a PC running Windows).
•
Configure the terminal simulator as follows:
o
115.200bps
o
8 data bits
o
1 stop bit
o
parity none
o
flow control none
o
Terminal emulation VT-100
•
Establish the connection and press <enter>
•
The default username (login) and password are ge and ge
•
A command-line configuration interface is entered. Type menu to enter the quick network
configuration menu
Note: Although the console interface provides a full set of commands, access using the serial connection
is only needed for initial configuration when no DHCP server is available, or the IP-address is unknown.