FIG 72 – BATTERY TRAY REMOVAL
5.
Unpack the 2 new battery trays from their boxes.
6.
Place the battery trays side by side in front of the battery compartment, aligning the rear
connector to the front panel.
7.
Slide the battery tray into the battery compartment and reconnect the DC cabling on each
battery tray. Affix the 2 battery brackets with the screws to hold the battery trays in the UPS
cabinet.
8.
Fix the battery grille by tightening screws.
9.
Re-install the two front covers.
NOTE
To avoid battery malfunction, in case of additional batteries connected, all battery packs
have to be replaced! It’s not possible to replace only 1 pack. Avoid connection between
new and old battery packs.
Power Unit Maintenance
For maintenance purposes, the power unit can be replaced while output is transferred to manual
bypass. See the following detailed steps for the replacement procedure.
WARNING
The UPS has to be switched to manual bypass before power unit replacement, otherwise
output power is lost.