XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation
Page 71
SPECIFICATIONS
MODEL
XPRT-6kVA
XPRT-10kVA
INPUT
Voltage
240/120V, 208/120V, 230/115V, 200/100V
Capacity VA (W)
6000 VA (4200 W)
10000 VA (8000 W)
Frequency
40 – 79 Hz
Power Factor
Greater than 0.97
Topology
True on-line, Double conversion, Input PF correction, auto bypass
OUTPUT
Voltage
240/120V, 208/120V, 230/115V, 200/100V (selectable) ± 5%
Frequency
50/60 Hz auto sensing ± 5% or frequency converter
Harmonic distortion
< 3% with linear load; < 5% with non-linear load
Wave form
≤ 5%
at full non-linear load;
≤ 3
% at full linear load
Efficiency AC/DC/AC
Greater than 86%
Auto Restart
Yes
Start on Battery
Yes
Overload Capacity
110% for 300 sec; 130% for 30 sec; 200% for 5 sec
Crest Factor
≤ 3 : 1
at full load
BATTERY
Battery Type
(12) 8AH / 144VDC
(24) 8AH / 288VDC
Recharge Time
< 3 hours to 90%
Backup Time in min.
½ LOAD
FULL LOAD
½ LOAD
FULL LOAD
UPS
14
5
16
6
+ (1) BP
34
14
39
17
+ (2) BP
58
25
66
28
+ (3) BP
82
36
92
41
+ (4) BP
105
47
119
54
PHYSICAL
Dimensions
W x D x H (inches)
W x D x H (inches)
Unit Dimensions
16.9" x 22.5" x 6.9" (4U)
16.9" x 26.0" x 10.5" (6U)
Unit Weight
162 lbs
309 lbs
Input Connection
L14-30P or HARDWIRE
HARDWIRE
Output Connection
PDU (4) 5-20R + (1) L6-30R + (1) L14-30R
or
HARDWIRE
HARDWIRE
or Optional PDU
(4) 5-20R + (2) L5-20R + (2) L6-30R
Communication
Interface
RS-232 and USB standard, SNMP (optional card)
Battery Pack
Dimensions
16.9” x 22.5” x 3.5” (2U)
16.9” x 26.0” x 6.8” (4U)