NXRT
‐
1000,
NXRT
‐
1500,
NXRT
‐
2000,
NXRT
‐
3000
USER’S
MANUALUNINTERRUPTIBLE
POWER
SUPPLY
(UPS)
Remote
Emergency
Power
Off
(REPO)
Port
A
customer
supplied
switch
located
remotely
can
be
used
to
open
the
REPO
connection
and
allows
the
UPS
output
receptacles
to
be
switched
off.
Since
the
REPO
shuts
down
the
equipment
immediately,
orderly
shutdown
procedures
are
not
followed
by
any
power
management
software.
The
UPS
will
have
to
be
manually
restarted
in
order
to
regain
power
to
the
outlets
on
the
UPS.
DETERMINING
THE
POWER
REQUIREMENTS
OF
YOUR
EQUIPMENT
1.
Make
sure
the
total
Volt
‐
Amp
(VA)
requirements
of
your
connected
equipment
does
not
exceed
the
maximum
VA
rating
for
the
UPS.
The
maximum
VA
ratings
are
shown
in
the
Specifications
section
of
this
document.
2.
Ensure
that
the
equipment
plugged
into
the
battery
‐
powered
outlets
does
not
exceed
the
UPS
rated
capacity.
If
UPS
rated
capacities
are
exceeded,
an
overload
condition
may
occur
and
cause
the
UPS
to
shut
down
and
trip
the
circuit
breaker.
3.
If
the
power
requirements
of
your
equipment
are
listed
in
values
other
than
Volt
‐
Amps
(VA),
convert
Watts
(W)
or
Amps
(A)
into
VA
by
doing
the
calculations
below.
Note:
The
equation
below
only
calculates
the
maximum
amount
of
VA
that
the
equipment
can
use,
not
what
is
typically
used
by
the
equipment
at
any
given
time.
Users
should
expect
usage
requirements
to
be
approximately
60%
of
the
value
to
estimate
power
requirements:
Watts
(W)
x
1.43
=
_____
VA
or
_____
Amps
(A)
x
120
=
_____
VA
Add
the
totals
for
all
of
the
equipment
and
multiply
this
total
by
0.65
to
calculate
actual
power
requirements.
Note:
Many
factors
can
affect
the
amount
of
power
that
your
computer
system
will
require.
The
total
load
that
you
will
be
placing
on
the
battery
‐
powered
outlets
should
not
exceed
85%
of
the
UPS
capacity.
HARDWARE
INSTALLATION
GUIDE
Inspect
the
UPS
upon
receipt.
The
packaging
is
recyclable;
keep
it
for
reuse
or
dispose
of
properly.
Safety
Information
Information
presented
here
is
vital
to
all
personnel.
Please
read
all
Safety
information.
Storage
and
Transportation
[12]