NXRT
‐
1000,
NXRT
‐
1500,
NXRT
‐
2000,
NXRT
‐
3000
USER’S
MANUALUNINTERRUPTIBLE
POWER
SUPPLY
(UPS)
SPECIFICATIONS
120V MODEL
NXRT-1000
NXRT-1500
NXRT-2000
NXRT-3000
INPUT
Voltage
120 VAC (80 - 138V at 100% load) 60-138V at 40% load
Capacity VA (W)
1000 VA (700 W)
1500 VA (1050 W)
2000 VA (1400 W)
3000 VA (2100 W)
Frequency
50/60 Hz auto sensing
Power Factor
≥
0.97
Topology
True on-line, Double conversion, Input PF correction
OUTPUT
Voltage 120
VAC
Frequency
50/60 Hz auto sensing
THD (full load)
Linear
≤
5%; non-Linear
≤
10%
Wave Form
Sine wave, zero transfer time
Load Power Factor
0.7
Efficiency AC/DC/AC
≥
90%
Auto Restart
Yes
Start on Battery
Yes
Rated Current
8.3 A
12.5 A
16.6 A
25 A
Overload Capacity
110-150% for 30 sec,
≥
150% for 200 msec
Crest Factor
3:1 at full load
BATTERY
Battery Type (UPS)
(3) 12V 9 AH / 36V
(4) 12V 7.2 AH / 48V
(8) 12V 7.2AH / 96V
Backup Time
7-11 min (internal batteries) to 18 hours using External Battery Packs (EBP)
Extended Battery Packs
EBP1
EBP2
EBP3
Battery Type (EBP)
2 strings of (3) 12V
9 AH / 36V
2 strings of (4) 12V
7.2 AH / 48V
2 strings of (8) 12V 7.2 AH / 96V
Recharge Time
< 8 hours to 90%