VESDA
®
LaserFOCUS VLF-500 Product Guide
13
Typical Wiring To Fire Alarm Control Panel (FACP)
The diagram below shows the correct way to wire VESDA laser detectors to a conventional fire
alarm control panel (FACP). It also shows where an End Of Line (EOL) resistor is correctly
installed.
Figure 14 - Typical wiring to a fire panel with EOL
Wiring To an Address Loop Module.
This wiring example is for wiring VESDA detectors to a typical Address Loop module 3 input 1
output.
These are example drawings. Refer to the appropriate product manual for the exact
wiring details of the third party equipment
.
Figure 15 - Addressable Loop Module with EOL
Normally Closed (NC)
FIRE 1
Common (C)
Normally Open (NO)
Normally Closed (NC)
ACTION
Common (C)
Normally Open (NO)
Normally Closed (NC)
FAULT
Common (C)
Normally Open (NO)
GPI
(Set to reset)
(NC)
Reset (C)
(NO)
Input
Short = Fire
Open = Fault
Fire Panel (FACP)
Detector
EOL
To next detector
or EOL resistor
Normally Closed (NC)
FIRE 1
Common (C)
Normally Open (NO)
Normally Closed (NC)
ACTION
Common (C)
Normally Open (NO)
Normally Closed (NC)
FAULT
Common (C)
Normally Open (NO)
GPI
(Set to reset)
(NC)
Reset (C)
(NO)
Fire Input
Short = Fire
Open = Wiring Fault
3 output 1 input Loop Module
Detector
EOL
Pre Alarm
Short = Fire
Open = Wiring Fault
Fault Input
Short= Detector Fault
Open = Wiring Fault
EOL
EOL
EOL
To Next Detector
To FACP