VESDA-E VES-A10-P Product Guide
www.xtralis.com
81
7
Maintenance
To maintain the VES-A10-P detector at its peak performance level, the recommended maintenance schedule
shown in Table 7-1 below should be followed.
Table 7-1: Recommended maintenance schedule for the VES-A10-P detector
Maintenance Check
Quarterly
Six Monthly
Annual
Biennial
Power Supply and Battery
Check Pipe Network
Pipe Integrity Smoke Test
Check Pipe Flow
Clean Sampling Point
Flush Pipe Network
Replace Filter
Notes:
l
The above maintenance steps are preventative maintenance.
l
Maintenance can be conducted by the original installer or an authorized distributor or service contractor.
l
The required frequency of maintenance checks may vary depending upon local codes and standards and
the environment of the installation.
l
When smoke testing is done, follow the site procedures for preventing false alarms to monitoring
services.
Caution:
While the detector is disabled or put into Standby mode, no fire warnings will be annunciated by
the detector. Prior to any maintenance or testing:
l
Inform the appropriate supervising authority.
l
Ensure that any ancillary devices dependent on the detector are isolated before work
commences.
Attention :
Pendant que le detecteur ou la zone est desactivee, aucun feu d’indication va etre emis par le
detecteur. Avant tout entretien ou tester:
l
Informer les autorité de supervision appropriée.
l
S'assurer que tout les appareils auxiliaires dépendants sur le détecteur sont isolés avant
de commencer aucun travail.
7.1
Standby
When maintenance is performed on the pipe network or sample points it is recommended that you temporarily
set the detector to Standby in order to turn off the aspirator. Setting the VES-A10-P to Standby mode
deactivates the aspirator and stops all detection of alarms (but not detection and signaling of faults). Standby
mode is signaled on relay #1 and relay #3 by default. Other relays may also be configured to signal standby
mode. Refer to sections 4.3.6 and 5.5.12 for further information.
To set the detector to Standby mode using Xtralis VSC, select Go to Standby from the Device menu. The
Disabled LED will blink and the aspirator will turn off. If configured the buzzer will beep once per minute if the
Standby beep checkbox on the Relay configuration screen (section 5.5.12) is ticked.
To re-activate the unit, select End Standby from the Device menu.
Summary of Contents for VESDA-E VES-A10-P
Page 2: ......
Page 10: ...VESDA E VES A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 22: ...VESDA E VES A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Page 52: ...VESDA E VES A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 82: ...VESDA E VES A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Page 86: ...VESDA E VES A10 P Product Guide 80 www xtralis com This page is intentionally left blank ...
Page 103: ...VESDA E VES A10 P Product Guide www xtralis com 97 Figure 7 21 Undo Sampling Module screws ...
Page 108: ...VESDA E VES A10 P Product Guide 102 www xtralis com ...
Page 110: ...VESDA E VES A10 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 114: ...VESDA E VES A10 P Product Guide 108 www xtralis com This page is intentionally left blank ...
Page 120: ...VESDA E VES A10 P Product Guide 114 www xtralis com This page is intentionally left blank ...
Page 126: ...VESDA E VES A10 P Product Guide 120 www xtralis com Z zone 57 58 81 115 ...