screwdriver in the large slot and twist, or use a small screwdriver in the side slots to lever the plug out.
l
Insert the pipes into the pipe inlet(s) ensuring a firm fit.
Note:
DO NOT glue the inlet pipes to the pipe inlet manifold.
When configuring the detector ensure that the correct pipes in use are selected as indicated in Table 3-1.
No. of Pipes
Preferred Pipe Inlet Port to use
Pipe 1
Pipe 2
Pipe 3
Pipe 4
VES-A10-P
1
Inlet 2 or 3
Inlet 2 or 3
2
3
Inlet 1 or 4
Inlet 1 or 4
4
Table 3-1: Preferred use of pipe inlet ports
1
2
3
4
Figure 3-1: Pipe inlet port numbering
For code-specific information, refer to Codes and Standards Information for Air Sampling Smoke Detection on
page iii.
3.4
Managing the Exhaust Air
Air is expelled from the detector via the exhaust port at the bottom of the unit enclosure.
The air exhaust port is tapered to accommodate standard pipes of OD 25 mm (ID 21 mm) and to provide an
airtight seal. IPS ¾ inch pipes (1.05 inch OD) require an adaptor (VSP-961) as shown in Figure 3-2. If required,
connect an outlet pipe to the exhaust manifold. DO NOT glue this pipe to the exhaust manifold as this will void
the warranty.
Figure 3-2: Imperial Pipe Adaptor (VSP-961)
Where the detector is located outside the protected environment, it may be necessary to return the exhaust air
to the same environment. For example, where pressure differences exceed 50 Pa, or where hazardous
substances are present inside the protected environment. Return air pipes need to be as short as possible to
minimize the effect of airflow impedance in the return air pipe network.
Summary of Contents for VESDA-E VES-A10-P
Page 2: ......
Page 10: ...VESDA E VES A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 22: ...VESDA E VES A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Page 52: ...VESDA E VES A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 82: ...VESDA E VES A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Page 86: ...VESDA E VES A10 P Product Guide 80 www xtralis com This page is intentionally left blank ...
Page 103: ...VESDA E VES A10 P Product Guide www xtralis com 97 Figure 7 21 Undo Sampling Module screws ...
Page 108: ...VESDA E VES A10 P Product Guide 102 www xtralis com ...
Page 110: ...VESDA E VES A10 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 114: ...VESDA E VES A10 P Product Guide 108 www xtralis com This page is intentionally left blank ...
Page 120: ...VESDA E VES A10 P Product Guide 114 www xtralis com This page is intentionally left blank ...
Page 126: ...VESDA E VES A10 P Product Guide 120 www xtralis com Z zone 57 58 81 115 ...