Fan Settings. 

 

SPEED SETTING 

Fan speed is determined by the wiring on the Low Volt side of the transformer. Wire the 7-12V fan connection to the 7V 

terminal on the transformer for low speed, or the 12V transformer terminal for high speed. Alternately the fan can be wired 

with a change-over switch (as shown above – Fig. J) to allow speed to be changed after installation. 

  

LV100TR / LV100TS / LV100PIRR / LV100PIRS only. 

 

To adjust the over-run period turn the control (T) clockwise to increase and anti-clockwise to decrease – see Figure H.

 

 

LV100HTR / LV100HTS / LV100HPTR / LV100HPTS only – see figures H and I. 

 

The pre-set humidity operation is factory set at approximately 75% Relative Humidity (RH), but can be adjusted 

between 65% and 85% RH by control H. 

 

The over-run timer is factory set at 15 minutes but can be adjusted from 30 seconds to 30 minutes by control T. 

 

Turn the controls clockwise to increase RH or time and anti-clockwise to decrease. 

 

 

 

 

 

 

 

 

 

Summary of Contents for 93011AW

Page 1: ...et before commencing installation Do install each fan with a means for disconnection in all poles in the fixed wiring Do make sure the mains supply is switched off before attempting to make electrical...

Page 2: ...gral pull cord switch In automatic mode the built in timer automatically operates the fan for a pre set delay time from 30 seconds to 30 minutes once humidity drops below the pre set Relative Humidity...

Page 3: ...Back plate fixing positions Front Cover Removal Depress Cover Latch with tool remove Cover A C B...

Page 4: ...Minimum 30 seconds Maximum 30 minutes Factory settings Timer 15 minutes RH 75 D E H F G...

Page 5: ...Wiring and setting up I1...

Page 6: ...ract Refer to Building Regulations for specific requirements Exhaust air must not be discharged into a flue used for exhausting of fumes from appliances supplied with energy other than electric Requir...

Page 7: ...ated 2 core cable supply to transformer LV100R LV100S LV100PR LV100PS LV100HTR LV100HTS LV100HPTR LV100HPTS LV100PIRR LV100PIRS Suitably rated 3 core cable supply to transformer LV100TR LV100TS 1 Chec...

Page 8: ...e back plate to the wall ceiling using appropriate fasteners supplied See figure A 12 If using screws do not over tighten Mount the back draft shutter 13 Peel the backing from the foam strip supplied...

Page 9: ...ion LV100TR LV100TS LV100PIRR LV100PIRS only To adjust the over run period turn the control T clockwise to increase and anti clockwise to decrease see Figure H LV100HTR LV100HTS LV100HPTR LV100HPTS on...

Page 10: ...Automatic mode The fan automatically adjusts to slow changes in natural humidity levels without operating the fan If the humidity levels increase at a rate slower than 5 RH in 5 minutes up to the pre...

Page 11: ...This page has been left blank for the addition of any notes you may wish to make...