5
4.3. Specifications
Unless otherwise noted, specifications are warranted over the ambient temperature range of 0 to 40 ºC.
Notes:
1. Minimum voltage is guaranteed at greater than 1% of the rated output voltage.
2. Minimum current is guaranteed at greater than 1% of the rated output current.
3. Measured with 20 MHz bandwidth and excluding line frequency ripple (see application note AN024 for measurement details, these measurements taken at full rated
output voltage and full power.
4. Line frequency ripple measured with 20 MHz bandwidth (see application note AN024 for measurement details, these measurements taken at full rated output
voltage and full power.
5. Time for output voltage to recover within 0.5% of its rated output for a load change from 10 to 90% of its rated output current.
6. Voltage set point from 10% to 100% of rated output
7. Add this to the output response time to obtain the total programming time
8. Time to provide data back to the controller using LAN interface (does not include A/D conversion time)
PLS6003033 PLS6005020 PLS60010010 PLS6002005 PLS6004002.5
DC Output Ratings
(1)
Voltage
30 V
50 V
100 V
200 V
400 V
Current
33 A
20 A
10 A
5 A
2.5 A
Power
600 W
600 W
600 W
600 W
600 W
Output Ripple & Noise
CV p-p
3
60 mV
100 mV
100 mV
100 mV
200 mV
CV rms
4
20 mV
100 mV
150 mV
150 mV
50 mV
Load Regulation
(change from 10%-90% load)
Voltage
15 mV
25 mV
50 mV
100 mV
200 mV
Current
15 mV
15 mV
15 mA
15 mA
15 mA
Line Regulation
(change from 100-132 VAC input or
180-260 VAC input)
(5)
Voltage
15 mV
25 mV
50 mV
100 mV
200 mV
Current
15 mV
15 mV
15 mA
15 mA
15 mA
Programming Accurancy
(1,2)
Voltage 0.1%+
15 mV
25 mV
50 mV
100 mV
200 mV
Current 0.1%+
66 mA
40 mA
20 mA
10 mA
5 mA
Measurement Accuracy
Voltage 0.1%+
15 mV
25 mV
50 mV
100 mV
200 mV
Current 0.1%+
60 mA
40 mA
15 mA
10 mA
5 mA
Transient Recovery Time
(5)
Time
≤1 ms
≤1 ms
≤1 ms
≤1 ms
≤1 ms
Supplemental Characteristics
(supplemental characteristics are not warranted but are descriptions of typical performance determind
either by design or type testing)
Output Response Time
(settle to within ±1% of the rated
output, with resistive load)
Up, Full Load
0.08 s
0.08 s
0.08 s
0.08 s
0.08 s
Down, Full Load
0.08 s
0.08 s
0.08 s
0.08 s
0.08 s
Down, No Load
0.5 s
0.5 s
0.5 s
0.5 s
0.5 s
Command Response Time
(7)
50 ms
50 ms
50 ms
50 ms
50 ms
50 ms
Data Readback Transfer Time
(8)
5 ms
5 ms
5 ms
5 ms
5 ms
5 ms
Remote Sense Compensation
Volts/Load Lead
1 V
1 V
2 V
4 V
4 V
Over-voltage Protection
Range
0.5-33 V
0.5-55 V
0.5-110 V
0.5-220 V
0.5-440 V
Accuracy
0.3 V
0.5 V
1 V
2 V
4 V
Output Ripple & Noise
(3)
CC rms
7 mA
5 mA
5 mA
5 mA
10 mA
Programming Resolution
Measurement Resolution
Voltage 0.05%+
10 mV
25 mV
50 mV
100 mV
200 mV
Current 0.05%+
20 mA
20 mA
10 mA
5 mA
2.5 mA
Front Panel Display Accuracy
Voltage 0.1%+
10 mV
25 mV
50 mV
100 mV
200 mV
Current 0.1%+
33 mA
20 mA
10 mA
5 mA
2.5 mA