USER MANUAL - OPTIMA RT9W 1K/2K/3K 

 

 

www.xmart-ups.com 

VER.171130-WP+-ENG

 

 

5.

 

OPERATION MODES 

 

This is a True On Line Double Conversion UPS and it is designed to offer clean, bump-less and highest quality power to your computer 

related equipment protecting also your valuable data. Power delivered by UPS is 100% sine wave as main line. 

 

According to AC main service, and how UPS has been configured, it may operate in following modes: 

 

ONLINE NORMAL Mode  

When UPS is off by selecting ON push button in front panel UPS enters into ONLINE NORMAL mode if AC main service is inside acceptable 

input range. Under this mode UPS Inverter powers outputs and the energy is taken from DC voltage coming from AC/DC converter. Batteries 

are charged by AC Line if required. 

BATTERY Mode (Also known Inverter Mode) 

If under ONLINE NORMAL mode UPS detects a problem in AC input Line it enters in battery mode. Under this mode UPS takes energy 

from batteries to feed inverter that generates power for the output. There are no transfers neither micro-cuts on UPS output as inverter was 

already working. The only difference is that energy is now coming from batteries instead of rectifier output. Transfer time is actually Zero 

(0ms). UPS also can enter in battery mode when it is turned on without an acceptable AC input. 

STATIC BYPASS (INTERNAL BYPASS):

  

This mode can be adopted if UPS configuration allows BYPASS mode and any of 3 below conditions is present: 

Under bypass mode, UPS AC output is feed from UPS AC input. When UPS is in bypass mode, in case AC input is interrupted, output will 

be interrupted also and UPS will power off. No battery mode can be adopted from bypass mode. 

Bypass mode can be caused by any of below conditions: 

1-

 

Bypass mode is adopted, in case ON button has not been activated as soon as UPS detects a valid AC input on its terminals. 

(If bypass mode is not enable, UPS will simply light its LCD. Outputs will keep powered off)  

2-

 

Bypass mode is adopted as soon as a problem is detected in its internal circuitries. 

3-

 

Bypass mode is also activated in case an external overload is detected in UPS output. It happens when equipment connected 

to UPS output requires a power higher than max. power of the UPS 

 

Additionally, this UPS can adopt under operator demand other operation modes as described: 

 

FREQUENCY CONVERSION:

 

 

 

 

      

 

 

 

This UPS offers a very sophisticated function named frequency conversion (CF) that allows UPS to generate power output at determined 

frequency value (50Hz or 60Hz) no matter input frequency value. UPs will be able to generate output at 50Hz even input source is at 60Hz 

or generate 60Hz even if connected to 50Hz source. 

This function can be configured and activated by LCD. Revise configuration section of this manual. 

ECO:

  

Under this mode, UPS powers outputs from the AC input. This is a kind of supervised BYPASS mode. As soon as AC input is out of 

acceptable input range for ECO mode (as defined on LCD configuration menus), UPS switch UPS from ECO to ONLINE mode or battery 

mode. Online mode is adopted if input range is acceptable for ONLINE mode. Switching from ECO to other mode takes about 4ms to10ms. 

ECO mode must be activated on LCD according to configuration section of this manual. 

IMPORTANT NOTES: 

1.- Under CF mode, UPS will disable BYPASS mode. Since UPS has been configured to generate output with frequency value different to 

input frequency, BYPASS mode is disable to avoid a not acceptable frequency value at output. 

2.- When CF function is activated, maximum power output is de-rated to 60% of maximum nominal capacity. For example, for a 3KVA 

(2.7KW) model, when CF is activated maximum output is decreased to 1.8KVA (1.6KW). 

 

 

LCD SCREEN ACCORDING TO OPERATION MODE: (FOR 230VAC models) 

LCD screens for 120V models are similar to screens described in this section for 230V. 

 

MODO DE 
OPERACIÓN 

DESCRIPCIÓN 

PANTALLA LCD 

STANDBY 

 

A- When bypass is not allowed UPS output is 

powered-off (0V). It happens when UPS 

detects a valid input voltage but ON button has 

not been pressed. 

B- Flow chart indicates AC input is used to 

recharge batteries only. 

 

Summary of Contents for OPTIMA RT9W 1K

Page 1: ...n this manual is property of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or...

Page 2: ...ONS 2 PRODUCT DESCRIPTION 3 SAFETY QUALITY AND PERFORMANCE STANDARDS 4 INSTALLATION 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 UPS CONFIGURATION 8 ERROR ALARMS CODES 9 TROUBLESHOOTING 10 S...

Page 3: ...its own power outlets this could damage the unit permanently WARNING Do not connect AC motor based equipment without a careful sizing of the UPS based on inrush current instead of average current Inr...

Page 4: ...of this product as a part of a more complex system not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment It also could affect its per...

Page 5: ...y by these handles 1 Install black handles to the UPS 2 Make sure rack cabinet counts with required mounting guides 3 Place UPS on the guides and fix it to the cabinet using black handles VERTICAL MOU...

Page 6: ...must connect line neutral and ground to input terminal block using cables with required gauge to drive maximum rated current For 3KVA UPS in 120V wires must be minimum 12AWG for lengths shorter than...

Page 7: ...off 2 Bypass mode is adopted as soon as a problem is detected in its internal circuitries 3 Bypass mode is also activated in case an external overload is detected in UPS output It happens when equipme...

Page 8: ...y UPS inverter C AC input symbol must be turned off representing there is no valid AC input detected by UPS D Clock symbol lights and backup time is displayed on the screen BYPASS MODE A Input and out...

Page 9: ...R UPS TURN OFF Press for 2 seconds to turn UPS off ENTER When UPS is in configuration mode this key operates as ENTER SELECT CHECK VALUES UPS can show in alternative cycle all available values by push...

Page 10: ...INFORMATION It displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also shows...

Page 11: ...5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area displays graphically by a 4 segments bar the power supplied by the UPS 25 Supplied Power...

Page 12: ...configuration mode LCD displays ID of the menu and values of 2 adjustable parameters 1 MENU ID 2 Function name 3 Configurable value KEYBOARD IN CONFIGURATION MODE ON MUTE Used as key to navigate or ch...

Page 13: ...F 50 50Hz CF 60 60Hz 04 ECO ENABLE DISABLE ENA ENABLE DIS DISABLE Factory set DIS Check more details at operation modes section 05 ECO INPUT VOLTAGE RANGE Vac Function 02 High Limit Function 03 Low Li...

Page 14: ...n Funci n de Convertidor de Frecuencia CH Charger Cargador de Bater as ESC Escape Salir ON ON Encendido ENA Enable Habilitado DIS Disable Des habilitado HLS High Loss L mite superior del rango LLS Low...

Page 15: ...ms are generated when UPS detects an abnormal situation but UPS can continue working in ONLINE mode However it is important operator revise condition that generated alarms and take actions to solve it...

Page 16: ...ON ERROR CODE ERROR SYMBOL DC BUS start failure 01 DC BUS High 02 DC BUS Low 03 DC BUS Unbalanced 04 INVERTER start failure 11 INVERTER High voltage 12 INVERTER Low voltage 13 SHORT CIRCUIT detected a...

Page 17: ...f not solved call technical service ERROR CODES PROBABLE CAUSE SOLUCION 01 02 03 04 Turn off and power off UPS Disconnect all equipment connected to UPS Restart UPS with no loads connected to its outp...

Page 18: ...eratures will short dramatically battery life IMPORTANT RECHARGING PLAN FOR LONG STORAGE If UPS will be stored for long time it is mandatory to recharge UPS periodically If UPS is not recharged accord...

Page 19: ...3 BATTERIES 36VDC MODELS 1 5KVA 1 Remove old batteries 2 Connect 2 batteries in series 3 Install new batteries in the binder 4 Close binder BATTERY REPLACEMENT 4 BATTERIES 48VDC MODELS 2KVA 1 Remove o...

Page 20: ...ion service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out...

Page 21: ...rotected sockets in Out C SELECT 6 Not used D OFF ENTER 7 USB RS232 ports 1 Standard UPS outlets 8 Intelligent SNMP port 2 IEC C20 outlet 16A IEC model only 9 External Battery connector optional in so...

Page 22: ...INDEX USER MANUAL OPTIMA RT9W 1K 2K 3K www xmart ups com VER 171130 WP ENG 22...

Page 23: ...INDEX USER MANUAL OPTIMA RT9W 1K 2K 3K www xmart ups com VER 171130 WP ENG 23...

Page 24: ...12V 9AH 6 x 12V 9AH 27 4 VDC 1 54 7 VDC 1 82 1 VDC 1 276 491 737 100 105 warning 105 110 10min to bypass 110 130 1min to bypass 100 105 warning 105 110 10min to bypass 110 130 1min to bypass 110 120 3...

Page 25: ...ows to set output frequency at constant value 50Hz or 60Hz El modo de Conversi n de Frecuencia permite fijar la salida a 50 o 60Hz Runtime for loads 80 is limited to 4min For loads between 70 and 80 r...

Page 26: ...INDEX USER MANUAL OPTIMA RT9W 1K 2K 3K www xmart ups com VER 171130 WP ENG 26 NOTAS...

Page 27: ......

Page 28: ...NW 26th St Doral FL 33172 USA sales xmart ups com EUROPE Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain sales xmart ups com Latin America Zona Ind San Vicente II C F A11 Maracay Venezuela sales xmart...

Reviews: