8.
ALARM & ERROR CODES
IMPORTANT:
All alarms and errors are informed on the LCD by dedicated codes and symbols.
▪
ALARMS: Are usually represented by blinking codes or symbols. Audible alarm beeps are also intermittent for
alarms. Alarm states do not avoid UPS works in ONLINE mode.
▪
ERRORS: Are usually represented by steady codes or symbols. Audible alarm for errors always sounds
continuously. Error states force UPS to go to Static Internal BYPASS mode.
ALARMS
Alarms are generated when UPS detects an abnormal situation, but UPS can continue working in ONLINE mode. However, it is important
operator revise condition that generated alarms and take actions to solve it. Alarms are represented by blinking symbols and codes with
intermittent beeps.
ALARM
ALARM SYMBOLS
AUDIBLE BEEP
OVERLOAD detected at UPS output
2 beeps / s
LOW BATTERY
1 beep / s
BATTERY DISCONNECTED OR FAULTY
1 beep / s
BATTERY REPLACEMENT REQUIRED
1 beep / s
BATTERY DISCONNECTED
1 beep / s
BATTERY OVER-VOLTAGE
1 beep / s
OVER TEMPERATURE
1 beep / s
BATTERY CHARGER FAILURE
1 beep / s
UPS IN BYPASS BUT INPUT VOLTAGE OUT OF
RANGE
1 beep / s
UPS IN BYPASS BUT INPUT FREQUENCY OUT OF
RANGE
1 beep / s
FAN FAILURE
1 beep / s
EEPROM MEMORY ERROR
1 beep / s