INDEX

 

USER MANUAL - OPTIMA RT9W 1K/2K/3K 

 

 

www.xmart-ups.com 

VER.171130-WP+-ENG

 

 

1.

 

GENERAL SAFETY INSTRUCTIONS 

 

WARNING

: It is required to read and understand this manual. Follow all instructions given in this manual for starting up and operating this 

product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for future consults. 

UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or negligent practices at the 

moment of install, starting up or maintain this product. UPS manufacturer or distributor is not liable for any damage that might rise from 

misusing this unit or defective installation.  

 

 

ELECTRIC SHOCK RISK

 

This product operates with dangerous voltages. It must be installed, operated and maintained ONLY by qualified technicians trained for 

this kind of products. Service personnel MUST know and understand very well all electric risks related to this product. 
If you are not qualified technician do not try to install, operate or repair this product. 

CAUTION:

 There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power line. 

CAUTION:

 Inside this equipment, due to internal batteries, there are ALWAYS dangerous voltages, EVEN the UPS is OFF and unplugged. 

CAUTION:

 There are dangerous voltages in internal DC Capacitors. Wait at least 10 minutes after turning off UPS before opening it to 

access inside. 

CAUTION:

 Power off UPS and unplugged it from AC Line before opening it to access inside this unit. 

CAUTION:

 Before starting the opening procedure, remove all jewelry and metallic objects such as: Rings, Watches, Bracelets, etc., because 

they could contact conductive parts and components inside the UPS and this might cause discharges and/or short circuits. Make sure 

using tools properly isolated to avoid electrical risks. 

WARNING:

 This product has been designed to be used indoors protected from water, direct sun light, dust and extreme temperature. 

WARNING:

 Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation. 

WARNING:

 This UPS must be connected to appropriate electrical service according to selected model. Technical specs label in the UPS 

shows the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently. 

WARNING:

 Do not connect AC motor based equipment without a careful sizing of the UPS based on inrush current instead of average 

current. Inrush current typical of motor based system could overload this UPS. 

WARNING:

 In case of emergency, power-off UPS and turn it off by <OFF> button in front panel. Then call technical service. 

 

 

INFORMATION FOR THE PROTECTION OF ENVIROMENT 

 UPS SERVICING

 

This  UPS  and  batteries  make  use  of  components  dangerous  for  the  environment  (electronic  cards,  electronic  components).  The 

components removed must be taken to specialized collection and disposal centers. 

 

NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES 

This product has been supplied from an environmentally aware manufacturer that complies with Waste Electrical and Electronic 

Equipment (WEEE) Directive 2002/96/CE. The “crossed

-out wheel

ie bin” symbol at left is placed on this product to encourage 

you to recycle wherever possible. Please be environmentally responsible and recycle this product through your recycling facility 

at its end of life. Do not dispose  of this product as unsorted municipal waste. Follow local municipal waste electrical and 

electronic equipment (WEEE). 

 

 

2.

 

PRODUCT DESCRIPTION 

 

This is an Uninterruptible Power Supply (UPS) ONLINE DOUBLE CONVERSION with IGBT technology at rectifier and inverter stages with 

PWM modulation. It generates a pure SINEWAVE output free of noise and imperfections for powering and protecting your valuable system. 

This UPS is the right choice to protect hardware and data in critical workstations and server applications. 

This product has been designed to operate under hostile electrical conditions but offering a reliable performance with outstanding features 

and characteristics. Optima RT9W is equipped with a powerful anti-surge system based on MOV technology. This model has filtering 

circuits for EMI interferences. It is 100% compatible to operate connected to low quality AC sources like power generators. Soft-start 

function allows connection to AC input source is done only when AC input values are confirmed inside operational ranges. 

Our  monitoring  software  allows  configuring  and  controlling  this  UPS  by  any  of  available  communications  ports:  USB/RS232  or  LAN 

Ethernet optional card (under SNMP protocol). 

 

 

OPTIMA RT9W series has 4 different models for supporting all kind of applications from 1KVA to 3KVA: 

 

RT9W 1K: 1.000VA/900W 

RT9W 2K: 2.000VA/1.800W 

RT9W 3K: 3.000VA/2.700W 

 

Summary of Contents for OPTIMA RT9W 1K

Page 1: ...n this manual is property of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or...

Page 2: ...ONS 2 PRODUCT DESCRIPTION 3 SAFETY QUALITY AND PERFORMANCE STANDARDS 4 INSTALLATION 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 UPS CONFIGURATION 8 ERROR ALARMS CODES 9 TROUBLESHOOTING 10 S...

Page 3: ...its own power outlets this could damage the unit permanently WARNING Do not connect AC motor based equipment without a careful sizing of the UPS based on inrush current instead of average current Inr...

Page 4: ...of this product as a part of a more complex system not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment It also could affect its per...

Page 5: ...y by these handles 1 Install black handles to the UPS 2 Make sure rack cabinet counts with required mounting guides 3 Place UPS on the guides and fix it to the cabinet using black handles VERTICAL MOU...

Page 6: ...must connect line neutral and ground to input terminal block using cables with required gauge to drive maximum rated current For 3KVA UPS in 120V wires must be minimum 12AWG for lengths shorter than...

Page 7: ...off 2 Bypass mode is adopted as soon as a problem is detected in its internal circuitries 3 Bypass mode is also activated in case an external overload is detected in UPS output It happens when equipme...

Page 8: ...y UPS inverter C AC input symbol must be turned off representing there is no valid AC input detected by UPS D Clock symbol lights and backup time is displayed on the screen BYPASS MODE A Input and out...

Page 9: ...R UPS TURN OFF Press for 2 seconds to turn UPS off ENTER When UPS is in configuration mode this key operates as ENTER SELECT CHECK VALUES UPS can show in alternative cycle all available values by push...

Page 10: ...INFORMATION It displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also shows...

Page 11: ...5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area displays graphically by a 4 segments bar the power supplied by the UPS 25 Supplied Power...

Page 12: ...configuration mode LCD displays ID of the menu and values of 2 adjustable parameters 1 MENU ID 2 Function name 3 Configurable value KEYBOARD IN CONFIGURATION MODE ON MUTE Used as key to navigate or ch...

Page 13: ...F 50 50Hz CF 60 60Hz 04 ECO ENABLE DISABLE ENA ENABLE DIS DISABLE Factory set DIS Check more details at operation modes section 05 ECO INPUT VOLTAGE RANGE Vac Function 02 High Limit Function 03 Low Li...

Page 14: ...n Funci n de Convertidor de Frecuencia CH Charger Cargador de Bater as ESC Escape Salir ON ON Encendido ENA Enable Habilitado DIS Disable Des habilitado HLS High Loss L mite superior del rango LLS Low...

Page 15: ...ms are generated when UPS detects an abnormal situation but UPS can continue working in ONLINE mode However it is important operator revise condition that generated alarms and take actions to solve it...

Page 16: ...ON ERROR CODE ERROR SYMBOL DC BUS start failure 01 DC BUS High 02 DC BUS Low 03 DC BUS Unbalanced 04 INVERTER start failure 11 INVERTER High voltage 12 INVERTER Low voltage 13 SHORT CIRCUIT detected a...

Page 17: ...f not solved call technical service ERROR CODES PROBABLE CAUSE SOLUCION 01 02 03 04 Turn off and power off UPS Disconnect all equipment connected to UPS Restart UPS with no loads connected to its outp...

Page 18: ...eratures will short dramatically battery life IMPORTANT RECHARGING PLAN FOR LONG STORAGE If UPS will be stored for long time it is mandatory to recharge UPS periodically If UPS is not recharged accord...

Page 19: ...3 BATTERIES 36VDC MODELS 1 5KVA 1 Remove old batteries 2 Connect 2 batteries in series 3 Install new batteries in the binder 4 Close binder BATTERY REPLACEMENT 4 BATTERIES 48VDC MODELS 2KVA 1 Remove o...

Page 20: ...ion service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out...

Page 21: ...rotected sockets in Out C SELECT 6 Not used D OFF ENTER 7 USB RS232 ports 1 Standard UPS outlets 8 Intelligent SNMP port 2 IEC C20 outlet 16A IEC model only 9 External Battery connector optional in so...

Page 22: ...INDEX USER MANUAL OPTIMA RT9W 1K 2K 3K www xmart ups com VER 171130 WP ENG 22...

Page 23: ...INDEX USER MANUAL OPTIMA RT9W 1K 2K 3K www xmart ups com VER 171130 WP ENG 23...

Page 24: ...12V 9AH 6 x 12V 9AH 27 4 VDC 1 54 7 VDC 1 82 1 VDC 1 276 491 737 100 105 warning 105 110 10min to bypass 110 130 1min to bypass 100 105 warning 105 110 10min to bypass 110 130 1min to bypass 110 120 3...

Page 25: ...ows to set output frequency at constant value 50Hz or 60Hz El modo de Conversi n de Frecuencia permite fijar la salida a 50 o 60Hz Runtime for loads 80 is limited to 4min For loads between 70 and 80 r...

Page 26: ...INDEX USER MANUAL OPTIMA RT9W 1K 2K 3K www xmart ups com VER 171130 WP ENG 26 NOTAS...

Page 27: ......

Page 28: ...NW 26th St Doral FL 33172 USA sales xmart ups com EUROPE Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain sales xmart ups com Latin America Zona Ind San Vicente II C F A11 Maracay Venezuela sales xmart...

Reviews: