27
power is cut (No battery).
※
3. The serial number of input coil and output relay are octal data, other memorizers’
number are all decimal data.
※
4. There is no I/O point connected with exterior device can be used as interior relay.
Soft component power failure area setting:
XP1/XMP1:
Soft
component
Area
Function
Default value
Power failure
memory area
D
FD8202
First address of the power
failure memory area of D
100
D100~D149
M
FD8203
First address of the power
failure memory area of M
200
M200~M319
T
FD8204
First address of the power
failure memory area of T
640
No set
C
FD8205
First address of the power
failure memory area of C
320
C320~C631
S
FD8206
First address of the power
failure memory area of S
512
S0~S31
XP2/XMP2:
Soft
component
Area
Function
Default value
Power failure
memory area
D
FD8202
First address of the power
failure memory area of D
4000
D4000~D4999
M
FD8203
First address of the power
failure memory area of M
3000
M3000~M7999
T
FD8204
First address of the power
failure memory area of T
640
No set
C
FD8205
First address of the power
failure memory area of C
320
C320~C639
S
FD8206
First address of the power
failure memory area of S
512
S512~S1023
XP3/XMP3:
Soft
component
Area
Function
Default value
Power failure
memory area
D
FD8202
First address of the power
failure memory area of D
4000
D4000~D7999
M
FD8203
First address of the power
failure memory area of M
3000
M3000~M7999
T
FD8204
First address of the power
failure memory area of T
640
No set