26
XP2/XMP2 and XP3/XMP3 series:
Range
Point
Soft
component
Name
XP2/XMP2
XP3/XMP3
XP2/XMP2 XP3/XMP3
X
Input point
X000~X011(octal)
10
Y
Output
point
Y000~Y007(octal)
8
M0~ M2999
【
M3000~M7999
】
8000
M
Auxiliary
relay
M8000~M8767
768
S
Status
S0~ S511
【
S512~M1023
】
1024
T0~T99
:
100ms not accumulation
T100~T199
:
100ms accumulation
T200~T299
:
10ms not accumulation
T300~T399
:
10ms accumulation
T400~T499
:
1ms not accumulation
T500~T599
:
1ms accumulation
T600~T618
:
1ms with interruption precise time
T
Timer
T620~T639
:
vacant
640
C0~C299
:
16 bits forth counter
C300~C318
:
32 bits forth/back counter
【
C320~C598
】
:
32 bits forth/back counter
【
C600~C619
】
:
one phase high speed counter
【
C620~C629
】
:
Pulse + direction high speed
counter
C
Counter
【
C630~C639
】
:
AB phase high speed counter
640
D0~D999
【
D4000~D4999
】
D0~ D3999
【
D4000~D7999
】
2000
8000
D
Data
register
For special using
D8000~D8511
D8630~D8729
For special using
D8000~D9023
612
1024
FD0~FD127
FD0~FD1535
128
1536
FD
FlashROM
register
For special using
FD8000~FD8383
For special using
FD8000~FD8511
384
512
ED
Extend data
register
-
【
ED0~ED16383
】
-
16384
NOTE:
※
1. The memorizer area in
【
】
is the defaulted power failure retentive area, the power
failure retentive area of soft components D, M, S, T, C can be set via FD register. For
the details, please see the following table.
※
2. Flash ROM register needn’t set power failure retentive area, its data won’t lose when