![Xinje XD Series User Manual Download Page 149](http://html.mh-extra.com/html/xinje/xd-series/xd-series_user-manual_887444149.webp)
148
2. Operands
Operands Function
Data Type
S
The source data address
16 bits, BIN
D
The decode result head address
16 bits, BIN
n
The decoding soft element bit quantity
16 bits, BIN
3. Suitable soft components
*Notes: D includes D, HD; TD includes TD, HTD; CD includes CD, HCD, HSCD, HSD;
DM includes DM, DHM; DS includes DS, DHS.
M includes M, HM, SM; S includes S, HS; T includes T and HT; C includes C and HC.
< When is bit unit > n≤16
DX0
DECO
M10
K3
X10
n
S·
D·
1
0
1
0
1
0
0
0
0
0
X2
X1
X0
M17
M16
M15
M14
M13
M12
M11
M10
7
6
5
4
2
1
0
4
0
2
1
3
N = 3, so the decoding object is the lower three bits in DX0, which are X2 ~ X0.
N = 3, so the decoding results need to be expressed by 2
3
= 8 bits, which are M17 ~ M10.
When X2 = 1, X1 = 0, X0 = 1, the value it represents is 4 + 1 = 5, so M15 in the fifth place
from M10 changes to 1; when X2 ~ X0 is all zero, the value is 0, so M10 is 1 (M10 is the 0th
place).
If n = 0, the instruction will not be executed. If n is the value out of 0 ~ 16, the instruction
will not be executed.
When n = 16, if the decoding command is a bit soft component, the number of points is
2 ^ 16 = 65536.
When the driver input is OFF, the instruction is not executed, and the decoding output of the
action is maintained.
Operand
System
Constant Module
D
*
FD
TD
*
CD
*
DX
DY
DM
*
DS
*
K /H
ID
QD
S
●
●
●
●
●
●
●
●
n
●
Word
Operand
System
X
Y
M
*
S
*
T
*
C
*
Dn.m
D
● ● ●
● ● ●
Bit
Description
D·
D·