Action display
LED lamp lights when output relay’s coils galvanize, output contacts are ON.
Response time
From the output relay galvanize (or cut) to the output contacts be ON (or OFF),
the response time is about 10ms
Output current
The current-voltage below AC250V can drive the load of pure resistance 2A/1
point
、
inductance load below 80VA
(
AC100V or AC200V
)
and lamp load below
100W
(
AC100V or AC200V
)
.
Open circuit’s leak current
When the output contact be OFF and there’s no leak current
,
can directly drive Ne
lamp etc.
The life of relay output contacts
Standard life of induce AC load such as contactor
、
electromagnetism valve
:
5
million times for 20VA load. Cut power device’s life according to the company’s
test: for 80VA load, the action life is up to 2 million times. But if the load parallel
connection with surge absorber, the life will be greatly improved.
Output Connection
Example
2