Appendix special soft device list
CH Nr.
DA
signal
-
-
-
-
0CH
QD100
-
-
-
1CH
QD101
-
-
-
XC-E2AD2PT2DA
RELATIVE
PARAMETERS
COMMENTS AND DESCRIPTIONS
CH
PT0
(
0.01
℃
)
PT1
(
0.01
℃
)
AD0
AD1
Display temperature
(unit: 0.1
℃
)
module 1
ID100
ID101
ID102
ID103
PID output
(X input which returns
to main unit)
module 1
X100
X101
X102
X103
Connecting status
(0 is connect, 1 is
disconnect)
module 1
X110
X111
X112
X113
PID auto tune error bit
(0 is normal, 1 is
parameters error)
module 1
X120
X121
X122
X123a
Enable channel’s
signal
module 1
Y100
Y101
Y102
Y103
Auto tune PID control
bit
Auto tune activate signal, enter auto tune stage if being set to be 1;
when auto turn finish, PID parameters and temperature control cycle value are refreshed,
reset this bit automatically.
Users can also read its status; 1 represents auto tune processing; 0 represents no atto tune or
auto tune finished
PID output value
(operation value)
Digital output value range: 0
~
4095
If PID output is analogue control (like steam valve open scale or thyistor ON angle),
transfer this value to the analogue output module to realize the control requirements
PID parameters
(P
、
I
、
D)
Via PID auto tune to get the best parameters;
If the current PID control can’t fulfill the control requirements, users can also write the PID
parameters according to experience. Modules carry on PID control according to the set PID
parameters.
PID operation range
(Diff)
(unit: 0.1
℃
)
PID operation activates between ±Diff ranges. In real temperature control environments, if
the temperature is lower than
, PID output the max value; if the temperature
is higher than
, PID output the mini value;
Temperature difference
δ
(sample temp Temperature difference δ)/10=display temperature value. Then
temperature display value can equal or close to the real temperature value. This parameter