1
The initial value is the value of F0.08 , it can change
the setup frequency value of the inverter by the
modification key of the operation panel (when the
LED keyboard displays output frequency or setup
frequency ) or UP and DW of the multifunctional input
terminals ; it can make a selection whether the current
frequency setup value is saved to F0.08 while power
off through setting F0.09 .
:
data
2
The frequency setup is determined by analog input
terminal AI1 , the input voltage range is
:
DC:0
10V
~
Group
Basic Function
F0
Display the software version of the machine
Setup range
Setup range
Setup range
0
V/ F Control
1
Reserved
0
Operation panel command channel
1
Terminal command channel
Terminal command channel
Operation panel disabled
Operation panel disabled
Operation panel ensabled
Operation panel enabled
2
3
Serial port communication
command channel
Serial port communication
command channel
4
Select the channel for inverter control command :
Control command includes start , stop , forward rotation ,
reverse rotation and Jog .
When parameter is set to 2/4
STOP enabled )
you can
press STOP key on the operation panel to stop ,if you want to
restart it , you must first input stop command by
multifunctional input terminal / Modbus interface, then
input running command .
(
,
As for the detailed setup method of terminal command
refer to the parameter explanation in F3.06, and refer to
EH600 serial communication protocol
.
《
》
to get the explanation
,please
about Modbus communication command
0
:
Running frequency is set by potentiometer on the
operation panel .
0
operation panel command channel
:
Perform running command control with keys on the
operation panel ,such as RUN
STOP
S keys .
、
、
1
2
terminal command channel
( ):
Perform running command control by the multifunctional
input terminals such as FWD
REV
JOGF
JOGR ,etc .
、
、
、
3
4
serial port command channel
( ):
The running command is sent by the host computer via the
communication mode . When selecting this item , it must be
used together with Modbus of Shenzhen XINLIN ELECTRIC
TECHNOLOGIES CO.,LTD.
Chapter 6 Parameter Description
43
Model
dependent
Factory
default value
Factory
default value
Factory
default value
Software version number
F0.00
F0.01
Control mode
0
Command source
selection
0
F0.02
Chapter 6 Parameter Description
Setup range
0
Panel potentiometer
1
2
AI1
3
AI2
Factory
default value
Model
dependent
Main frequency
source X selection
F0.03
Digital setup by UP and DW adjustment
(panel or external terminal)
PLC
PID
Communication reference
MS speed
PULSE setting(DI)
4
5
6
7
8
Select the input channel of the main reference frequency of
the inverter . There are nine types of main reference
frequency channels :
3
The frequency setup determined by analog input terminal
AI2 , it can be used as either voltage input or current input ,
which can be selected by the jumper .
:
DC Voltage range
0
10V
: ~
DC Current range
0
20mA
: ~
4
:
The frequency reference is given by external
terminal (DI) input pulse .
Frequency range
0
50kHz
Voltage range
5
30V
: ~
: ~
5: To select MS speed running mode, you need to set Group
F3
Input Terminal
and Group FB
MS Speed and
PLC
parameters to determine the relative relationship
between the reference signal and the reference frequency .
“
”
“
”
6
When the frequency source is simple PLC ,you need to set
Group FB
MS Speed and PLC
parameters to determine
the reference frequency ,veer and running time .
:
“
”
7
Select process PID control .In this case , you need to set
Group F9
PID Function
. The running frequency of
the inverter is based on the value after PID function .For
the meanings of PID reference source , reference quantity
and feedback source , please refer to Group F9
.
:
“
”
“
”
PID
Function