![Xilinx EH600 A Series User Manual Download Page 32](http://html1.mh-extra.com/html/xilinx/eh600-a-series/eh600-a-series_user-manual_3379127032.webp)
29
F2.00
V/F curve setup
0
straight V/F curve
:
1
0
1
multiple-point V/F curve
:
2
square V/F curve 1 1.5 time power
:
(
)
3
square V/F curve 2 2.0 time power
:
(
)
F2.01
V/F frequency point
F1
0.00Hz
F2
~
0.01Hz
0.00Hz
F2.02
V/F voltage point
V1
0.0%
V2
~
0.1%
0.0%
F2.03
V/F frequency point
F2
F1
F3
~
0.01Hz
F2.04
V/F voltage point V2
V1
V3
~
0.1%
F2.05
V/F frequency point
F3
F2
rated motor frequency
~
0.01Hz
F2.06
V/F voltage point V3
V2
100.0%
~
0.1%
F2.07
Torque boost
0.0%
automatic torque boost
:
0.1%
model
dependent
F2.08
Cutoff frequency of
torque boost
0
Maximum F0.11
~
0.01Hz
50.00Hz
F2.09
Slip compensation
coefficient
0
200%
~
1%
0%
○
F2.10
Automatic voltage
regulating (AVR)
selection
0
disabled
:
1
2
1
active
:
2
disabled only at the time of deceleration
:
F2.11
Oscillation
suppression gain
0
100
~
1
15
F2.12
Carrier frequency
1.0
15kHz
~
0.1kHz
model
dependent
○
○
25.00Hz
50.00Hz
50.0%
100.0%
○
○
V/F Control Parameters
Group
F2
0.1
20.0%
manual torque boost
~
:
Chapter 5 Function Parameter Table
Factory default
value
Function
code
Name
Setup range
Minimum unit
Modif-
ication
F2.13
Carrier frequency
adjustment selection
0
Fixed PWM
carrier frequency
temperature adjustment disabled
:
,
1
Random PWM
carrier frequency
temperature adjustment disabled
:
,
2
Fixed PWM
carrier frequency
temperature adjustment actived
:
,
3
Random PWM
carrier frequency
temperature adjustment actived
:
,
1
2
○