If the card was installed and validated successfully, a message similar to the following will be
displayed. Review the
Validation Summary
section at the end of the output and confirm the
device validated successfully. Additional validation details are displayed by appending the
--
verbose
option to the command. See
within the
for
support.
Starting validation for 1 devices
Validate Device : [0000:5e:00.1]
Platform : xilinx_u55c_gen3x16_xdma_base_2
SC Version : 7.1.14
Platform ID : FCC68C40-94CC-3A1E-9A6C-A76BCA494718
----------------------------------------------------------------------------
---
Test 1 [0000:5e:00.1] : PCIE link
Test Status : [PASSED]
----------------------------------------------------------------------------
---
Test 2 [0000:5e:00.1] : SC version
Test Status : [PASSED]
----------------------------------------------------------------------------
---
Test 3 [0000:5e:00.1] : Verify kernel
Test Status : [PASSED]
----------------------------------------------------------------------------
---
Test 4 [0000:5e:00.1] : DMA
Details : Host -> PCIe -> FPGA write bandwidth = 11937.2
MB/s
Host <- PCIe <- FPGA read bandwidth = 12076.0
MB/s
Test Status : [PASSED]
----------------------------------------------------------------------------
---
Test 5 [0000:5e:00.1] : iops
Details : IOPS: 462327 (verify)
Test Status : [PASSED]
----------------------------------------------------------------------------
---
Test 6 [0000:5e:00.1] : Bandwidth kernel
Details : Throughput (Type: HBM) (Bank count: 1) :
12098.7MB/s
Test Status : [PASSED]
----------------------------------------------------------------------------
---
Test 7 [0000:5e:00.1] : vcu
Validation completed. Please run the command '--verbose' option for more
details
Chapter 5: Card Bring-Up and Validation
UG1468 (v1.0) November 23, 2021
Alveo U55C Data Center Accelerator Card Installation Guide
22