Pressing the
5
and
6
buttons will scroll the display through all active fire conditions. More detailed
information (if applicable) can be viewed by pressing the panel’s more information button. To
return to the main access level 1 menu press the escape
3
button.
Display Fault Events
This function is only available if there are active faults on the system. If available, press the
accept
4
button once and a window similar to the one below will appear:-
Pressing the
5
and
6
buttons will scroll the display through all active faults. More detailed informa-
tion (if applicable) can be viewed by pressing the panel’s more information button. To return to the
main access level 1 menu press the escape
3
button.
Display Disablements
This function is only available when there are active disablements on the system. If available, press
the accept
4
button once and a window similar to the one below will appear:-
Pressing the
5
and
6
buttons will scroll the display through all active disablements. More detailed
information (if applicable) can be viewed by pressing the panel’s more information button. To
return to the main access level 1 menu press the escape
3
button.
Display Zones In Test
This function is only available if there are zones being tested. If available, press the accept
4
button
once and a window similar to the one below will appear:-
Pressing the
5
and
6
buttons will scroll the display through all zones in test mode. More detailed
information (if applicable) can be viewed by pressing the panel’s more information button. To
return to the main access level 1 menu press the escape
3
button.
Lamp test
This function tests the panel’s lamps (its LED indicators and display) to ensure they are working correctly.
When selected, press the accept
4
button and all of the panel’s LED indicators will illuminate steady
for approximately two seconds and its display will progressively block fill. The panel’s internal
sounder (if enabled) will also sound. Upon completion, the panel will return to the main access
level 1 menu. If any of the LEDs fail to illuminate or the display does not function correctly, report
the fault(s) to the designated site engineer and make a note of it in the fire system’s log book.
Display Alarm Counter
This function displays the total number of times the panel has been in a fire alarm condition. When
selected, press the accept
4
button once and the display will show the total number of times the
panel has been in a fire condition since it was installed AND the total number of times it has been in
alarm since its alarm counter was last cleared, for example:-
To return to the main access level 1 menu press the escape
3
or accept
4
button.
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 13 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Zone 1: Ground Floor
There are faults on this zone
1st Zone: 1: Shop floor
On: This Panel: Is Disabled
Zone 1: North Stairs
Is On Test
LAMP TEST?
Display Alarm Counter
AL1
Total Alarms = 12
Alarms since 01/01/05 = 7