background image

 

 

 

EN 

The specification table can be found in the appendix. 

The SR 200-12 / 24 is a microprocessor controlled separation relay 
specially developed for parallel charging of two batteries (or groups). Under 
certain voltage- and timer conditions the relay will switch on or off. In the 
switched-on position, the two batteries are linked together. However, if the 
measured voltage is not high enough, the relay will cut-off the connection. 
As a result, the two batteries cannot discharge each other. 

The relay is suitable for both 12Vdc and 24Vdc systems. However, the two 
batteries must have the same nominal voltage. It is also important that the 
two batteries are of the same kind. For example, it is not desirable to 
connect a LiFePO4 (lithium) battery with a lead battery. This is due to the 
large difference in the internal resistance. If the system is equipped with a 
Euro 5/6 alternator, then an isolating relay is not a workable solution and it 
is advisable to install a so-called charge converter. 

The maximum current that is allowed to flow through the relay is 200Amp. 
with a 12Vdc system and 100Amp. with a 24Vdc system.  
Because the voltage drop is almost zero, the operation of the separation 
relay will not be at the expense of the charging voltage. 
It is possible to force/manually connect the two batteries in parallel for a 
short period of time by means of an external contact. See paragraph "start 
assistance function". 

INSTALLATION

 

The relay automatically detects whether it is a 12Vdc or a 24Vdc system (0-
16Vdc = 12Vdc, 16-32Vdc = 24Vdc). That is why it is important that the 
batteries are at a normal voltage level at the time of connection. A too low 
or too high battery voltage can result in the wrong selection or that the 
voltage fault protection will intervene. 

Mounting

  

By using a screw, mount the relay vertically on a stable surface with the 
screw fixing facing up. Mounting in a different position will be at the expense 
of the IP value (dust and water tightness). 

Cable

 

thickness

 

Always keep the cables as short as possible. Use sufficiently thick (+) cables, 

Summary of Contents for SR 200-12

Page 1: ...SR 200 12 24 G e b r u ik s a a n w i j z i n g Pa gina 2 U s e r s m a n u a l Pa ge 6 G e b r a u c h s a n w e i s u n g Seite 10 NL EN DE...

Page 2: ...heidingsrelais geen werkbare oplossing en is het raadzaam om een z g laadomvormer te plaatsen De maximale stroom die door het relais mag lopen is 200Amp bij een 12Vdc systeem en 100Amp bij een 24Vdc s...

Page 3: ...le optimale kabeldikte kabel max stroom x lengte in meter x 0 2 kabeldikte mm totaal tussen de accu s De minuskabel moet minimaal 1 5mm zijn Aansluiting Koppel de minpolen van beide accu s los Volg qu...

Page 4: ...den om de accu s langer dan 30 seconden parallel te houden De aangeboden spanning mag tussen de 10 5 30Vdc liggen IN GEBRUIK Inschakelvoorwaarden Het relais schakelt in op het moment dat n van beide a...

Page 5: ...et relais zal niet in werking treden als het spanningsverschil tussen beide accu s meer dan 8Vdc is Niet alleen systeem en aansluitfouten worden hiermee ondervangen maar zeker ook het risico dat een k...

Page 6: ...and it is advisable to install a so called charge converter The maximum current that is allowed to flow through the relay is 200Amp with a 12Vdc system and 100Amp with a 24Vdc system Because the volt...

Page 7: ...in meter x 0 2 cable mm total distance between the batteries The minus cable must be at least 1 5mm Connection Disconnect the negative terminals from both batteries Follow the installation diagram be...

Page 8: ...only starts when the signal has disappeared so use a momentary switch When using a continuous switch you can choose to keep the batteries in parallel for longer than 30 seconds The voltage offered ma...

Page 9: ...ks the connection immediately the other battery and therefore also the possibly connected users are protect against this over voltage Voltage fault protection The relay will not operate if the voltage...

Page 10: ...usgestattet ist ist ein Trennrelais keine praktikable L sung und es wird empfohlen einen sogenannten Ladungswandler zu installieren Der maximale Strom der durch das Relais flie en darf betr gt 200 Amp...

Page 11: ...optimale Kabeldicke Kabel Max Strom Amp x L nge in Metern x 0 2 Kabeldicke mmq Gesamtabstand zwischen den Batterien Das Minuskabel muss mindestens 1 5 mm gro sein Anschluss Die Minuspole von beiden Ba...

Page 12: ...ine der beiden Batterien eine ausreichend hohe Spannung aufweist weil sie geladen wird 10 Sekunden lang 13 2 26 4Vdc oder 2 Sekunden lang 13 8 27 6Vdc Bei einer Starterbatterie handelt es sich normale...

Page 13: ...fferenz zwischen beiden Batterien mehr als 8Vdc betr gt Dadurch werden nicht nur System und Verbindungsfehler vermieden sondern auch die Gefahr dass eine defekte Batterie parallel geschaltet wird GARA...

Page 14: ...or 0sec PIN 30 of 87 22 0Vdc for 0sec 200mA 13 5Vdc 135mA 27Vdc based on 20 C if mounted according to the instructions Data subject to changes Number of batteries 2 SR 200 12 24 System voltage 12 and...

Page 15: ...Xenteq BV Banmolen 14 5768 ET Meijel NL Tel 31 77 4662067 info xenteq nl www xenteq nl V1C...

Page 16: ......

Reviews: