ADVANCED SETTINGS - TIMER FEATURE
33
INSTRUCTION MANUAL
::
Specify the number of minutes for which Stage 1 will function until Stage 2 is
activated to help raise (or cool) temperature (if the temperature set point is not
reached). This unique function avoids excess compressor wear in the case where
the necessary temperature set point is not met through setting of the Staging
Differential. Set to “00” to disable.
ADVANCED SETTINGS - DIFFERENTIAL SETTINGS
32
XCI
TSZ-1
>>
The XCI TSZ-1 allows you to control up to 2 Stages of Heating and 1 Stages of
Cooling, dependent on the type of system you have configured.
::
1ST STAGE DIFFERENTIAL
: Set temperature difference between temperature set
point and actual temperature reading before 1st stage heating or cooling is initiated.
::
2ND STAGE DIFFERENTIAL
: Set temperature difference between 1st stage initiation
and 2nd stage heating or cooling initiation.
::
OB ENERGIZED
: Reverses the Heat Pump OB Valve contact to HEAT or COOL
(manufacturer dependent).