Copyright | C6AM User Manual, Version 1.2.2
21
Left and right sides (3 x removable stainless-steel plates - one with reserved hole):
8 x M6 Philips flat head screws on each side (provided by XCHARGE)
Figure 4.3.5
4.4 Power Supply and Power Cable
Requirements for the power supply:
Power
Rated voltage
Rated current
Frequency
2 power modules
480V±10%, AC
90A
60Hz
4 power modules
480V±10%, AC
180A
60Hz
5 power modules
480V±10%, AC
225A
60Hz
5power modules
208V+10% AC
330A
60Hz
Table 4.4.1
Cable type: 3P+N+PE, shielded cables are optional if required by local law.
The optional cable shielding must be attached to the PE Rail at both ends of the cable.
The diameter of the cable conductor must be determined by your contractor /
electrician.